| Date |
Text |
| 2007-05-07 13:27:47 | ***DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEWS STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE |
| | PREVENTION CODE , 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 02.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, |
| | AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.)ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST |
| | DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS |
| | IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE |
| | FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. |
| | |
| | 04.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 06.)WHERE THE BUILDING IS PROTECTED BY FIRE |
| | PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED |
| | OPERATIONAL AT ALL TIMES DURING ALTERATION. |
| | |
| | 07.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES |
| | MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM |
| | SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED |
| | FOR REVIEW. |
| | |
| | 08.PLEASE SHOW THE LOCATION OF THE 2A:10BC FIRE |
| | EXTINGUISHERS SATISFYING THE 75' TRAVEL DISTANCE. |
| | |
| | 09.)ADDITIONAL PERMIT AND PLANS REQUIRED FOR |
| | MECHANICAL HOOD/SUPPRESSION SYSTEM. |
| | |
| | 10.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL |
| | FIRE ALARM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 8561-805-6722 |