2007-05-07 13:27:47***DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEWS STILL NEED TO BE ADDRESSED:
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE , 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST
 DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 04.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 06.)WHERE THE BUILDING IS PROTECTED BY FIRE
 PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING ALTERATION.
  
 07.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED
 FOR REVIEW.
  
 08.PLEASE SHOW THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHERS SATISFYING THE 75' TRAVEL DISTANCE.
  
 09.)ADDITIONAL PERMIT AND PLANS REQUIRED FOR
 MECHANICAL HOOD/SUPPRESSION SYSTEM.
  
 10.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW