| 2007-05-03 10:33:14 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER 561-805-6724 |
| | [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | COMMENTS FROM PREVIOUS REVIEWS, NOT PROPERLY |
| | ADDRESSED: |
| | |
| | |
| | 1.)A1.0 SHOWS "EXISTING FIRE RATED |
| | WALLS"; SPECIFY FIRE RATING. |
| | |
| | 3RD REVIEW ? A1.0 SHOWS A 4 HOUR WALL BETWEEN THE |
| | PROPOSED RESTAURANT AND MACY?S, AND A 2 HOUR WALL AT |
| | THE SHAFT.A1.1 SHOWS THE 4 HOUR WALL AS A 2 HOUR |
| | WALL.PLEASE ADDRESS. |
| | |
| | 2.)IS THIS A CHANGE OF OCCUPANCY? |
| | DECLARE GOVERNING CODE, FBC EB, AND |
| | LEVEL OF ALTERATION FBC EB 3, AND CHANGE |
| | OF OCCUPANCY IF APPLICABLE FBC 8. |
| | |
| | 3RD REVIEW ? THE ARCHITECT HAS DECLARED LEVEL 1 |
| | ALTERATION.SEE FBC EB CHAPTER 3.DOESN?T THIS |
| | INVOLVE ADDITION OF WINDOWS, RECONFIGURATION OF SPACE? |
| | THIS DOES NOT APPEAR TO BE A LEVEL 1 ALTERATION. |
| | |
| | 3.)PROVIDE A FIRE SPRINKLER PLAN, FBC*106.3.5.1.1(5), |
| | FS553.79(2). |
| | |
| | 3RD REVIEW ? THIS IS A STATUTORY REQUIREMENT; SEE |
| | ATTACHED LETTER.A 4X PLAN REVIEW FEE HAS BEEN |
| | CHARGED.THIS IS ALSO A STATUTORY REQUIREMENT; MUST BE |
| | CHARGED WHEN THE SAME COMMENT IS NOT ADDRESSED THREE |
| | TIMES AND IS REQUIRED TO BE CHARGED EACH TIME AFTER THE |
| | THIRD TIME. |
| | |
| | 4.)FBC TABLE 1004.1.2, PLAN STATES MOVEABLE SEATS, |
| | ARE THE TABLES FIXED?UNCONCENTRATED (TABLES & CHAIRS) |
| | IS 15 NET. |
| | |
| | 3RD REVIEW; OCCUPANT LOAD CANNOT BE LESS THAN THE |
| | TABLE, SO PLEASE ROUND UP RATHER THAN DOWN, INDOORS |
| | LESS BOOTHS CALCULATION. |
| | |
| | 5.)3RD REVIEW, FIRE RESISTANCE REQUIREMENTS ARE STILL |
| | NOT CLEAR.PLEASE SEE A1.1, DETAIL FOR UL U477, 2 HOUR |
| | BEARING WALL.I WAS UNABLE TO LOCATE THIS ASSEMBLY IN |
| | THE UL BOOK (HAS U476, U478, BUT NOT U477).THE |
| | DRAWING SHOWS THAT THIS IS A 1 HOUR WALL (BUT THE UL |
| | LISTING STATES IT IS A 2 HOUR) WITH 1 LAYER 5/8 TO |
| | CREATE A NEW 2 HOUR WALL.SEE FBC TABLE 721.2.1.4(2), |
| | 5/8 TYPE X HAS 40 MINUTE RATING, SO THIS WOULD NOT |
| | CREATE A 2 HOUR WALL.IT IS NOT CLEAR WHERE THIS WILL |
| | BE INSTALLED.SEE FBC TABLE 302.3.2, AND FBC302.3.2 |
| | EXCEPTION.IT IS ACCEPTABLE TO EXCEED MINIMUM CODE |
| | REQUIREMENTS, BUT DETAILS ARE TO CLEARLY SHOW CODE |
| | COMPLIANCE AND ARE TO BE CONSISTENT. |
| | |
| | 6.)A1.1 HAS A DETAIL WHICH IS NOT LABELED WITH A |
| | DETAIL MARKER NUMBER AND DOES NOT SPECIFY WHAT IT IS |
| | FOR OR WHAT THE FIRE RESISTANCE RATING IS.IS THIS A |
| | PART OF DETAIL 1?IT IS CLOUDED SEPARATELY. |
| | |
| | 7.)C1, ITEM 8, STATES TABLE 600 REQUIREMENTS. DECLARE |
| | BUILDING TYPE A OR B AND SHOW REQUIREMENTS BASED ON |
| | FBC2004, TABLE 601. |
| | |
| | 8.)PLEASE SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALCS, FBC 13 103.1. |
| | |
| | 9.)PROVIDE PRODUCT APPROVALS FOR THE COMPONENTS AND |
| | CLADDING.A1.0, WINDOW SCHEDULE NOTES WINDOW C AS |
| | EXISTING, AND IT APPEARS THAT WINDOWS A AND B ARE NEW. |
| | DOES THIS MEAN THAT ALL OF THE DOORS ARE NEW?IF NOT, |
| | NOTE THE DOORS AS EXISTING.IF THEY ARE, PROVIDE |
| | PRODUCT APPROVALS. |
| | |
| | 10.)DESIGNER OF RECORD IS TO REVIEW PRODUCT |
| | APPROVALS, FBC*106.3.3. |
| | |
| | ONE SET OF THE ARCHITECTURAL DRAWINGS HAS BEEN |
| | RETAINED. |
| | |
| | 6/07 - THE RETAINED SET WAS RETURNED TO THE PACKAGE |
| | (NEEDED DBPR STAMP). |
| | |