Plan Review Notes
Plan Review Notes For Permit 06081940
Permit Number 06081940
Review Stop B
Sequence Number 3
Notes
Date Text
2007-05-03 10:33:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER 561-805-6724
 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS REVIEWS, NOT PROPERLY
 ADDRESSED:
  
  
 1.)A1.0 SHOWS "EXISTING FIRE RATED
 WALLS"; SPECIFY FIRE RATING.
  
 3RD REVIEW ? A1.0 SHOWS A 4 HOUR WALL BETWEEN THE
 PROPOSED RESTAURANT AND MACY?S, AND A 2 HOUR WALL AT
 THE SHAFT.A1.1 SHOWS THE 4 HOUR WALL AS A 2 HOUR
 WALL.PLEASE ADDRESS.
  
 2.)IS THIS A CHANGE OF OCCUPANCY?
 DECLARE GOVERNING CODE, FBC EB, AND
 LEVEL OF ALTERATION FBC EB 3, AND CHANGE
 OF OCCUPANCY IF APPLICABLE FBC 8.
  
 3RD REVIEW ? THE ARCHITECT HAS DECLARED LEVEL 1
 ALTERATION.SEE FBC EB CHAPTER 3.DOESN?T THIS
 INVOLVE ADDITION OF WINDOWS, RECONFIGURATION OF SPACE?
 THIS DOES NOT APPEAR TO BE A LEVEL 1 ALTERATION.
  
 3.)PROVIDE A FIRE SPRINKLER PLAN, FBC*106.3.5.1.1(5),
 FS553.79(2).
  
 3RD REVIEW ? THIS IS A STATUTORY REQUIREMENT; SEE
 ATTACHED LETTER.A 4X PLAN REVIEW FEE HAS BEEN
 CHARGED.THIS IS ALSO A STATUTORY REQUIREMENT; MUST BE
 CHARGED WHEN THE SAME COMMENT IS NOT ADDRESSED THREE
 TIMES AND IS REQUIRED TO BE CHARGED EACH TIME AFTER THE
 THIRD TIME.
  
 4.)FBC TABLE 1004.1.2, PLAN STATES MOVEABLE SEATS,
 ARE THE TABLES FIXED?UNCONCENTRATED (TABLES & CHAIRS)
 IS 15 NET.
  
 3RD REVIEW; OCCUPANT LOAD CANNOT BE LESS THAN THE
 TABLE, SO PLEASE ROUND UP RATHER THAN DOWN, INDOORS
 LESS BOOTHS CALCULATION.
  
 5.)3RD REVIEW, FIRE RESISTANCE REQUIREMENTS ARE STILL
 NOT CLEAR.PLEASE SEE A1.1, DETAIL FOR UL U477, 2 HOUR
 BEARING WALL.I WAS UNABLE TO LOCATE THIS ASSEMBLY IN
 THE UL BOOK (HAS U476, U478, BUT NOT U477).THE
 DRAWING SHOWS THAT THIS IS A 1 HOUR WALL (BUT THE UL
 LISTING STATES IT IS A 2 HOUR) WITH 1 LAYER 5/8 TO
 CREATE A NEW 2 HOUR WALL.SEE FBC TABLE 721.2.1.4(2),
 5/8 TYPE X HAS 40 MINUTE RATING, SO THIS WOULD NOT
 CREATE A 2 HOUR WALL.IT IS NOT CLEAR WHERE THIS WILL
 BE INSTALLED.SEE FBC TABLE 302.3.2, AND FBC302.3.2
 EXCEPTION.IT IS ACCEPTABLE TO EXCEED MINIMUM CODE
 REQUIREMENTS, BUT DETAILS ARE TO CLEARLY SHOW CODE
 COMPLIANCE AND ARE TO BE CONSISTENT.
  
 6.)A1.1 HAS A DETAIL WHICH IS NOT LABELED WITH A
 DETAIL MARKER NUMBER AND DOES NOT SPECIFY WHAT IT IS
 FOR OR WHAT THE FIRE RESISTANCE RATING IS.IS THIS A
 PART OF DETAIL 1?IT IS CLOUDED SEPARATELY.
  
 7.)C1, ITEM 8, STATES TABLE 600 REQUIREMENTS. DECLARE
 BUILDING TYPE A OR B AND SHOW REQUIREMENTS BASED ON
 FBC2004, TABLE 601.
  
 8.)PLEASE SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALCS, FBC 13 103.1.
  
 9.)PROVIDE PRODUCT APPROVALS FOR THE COMPONENTS AND
 CLADDING.A1.0, WINDOW SCHEDULE NOTES WINDOW C AS
 EXISTING, AND IT APPEARS THAT WINDOWS A AND B ARE NEW.
 DOES THIS MEAN THAT ALL OF THE DOORS ARE NEW?IF NOT,
 NOTE THE DOORS AS EXISTING.IF THEY ARE, PROVIDE
 PRODUCT APPROVALS.
  
 10.)DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS, FBC*106.3.3.
  
 ONE SET OF THE ARCHITECTURAL DRAWINGS HAS BEEN
 RETAINED.
  
 6/07 - THE RETAINED SET WAS RETURNED TO THE PACKAGE
 (NEEDED DBPR STAMP).
  