| Date |
Text |
| 2007-01-24 12:38:41 | ***** UNSAT 2ND REVIEW ***** |
| | |
| | ITALIAN OVEN |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS |
| | STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO DO NOT SUBMIT LOOSE SHEETS NOT ATTACHED IN |
| | THE SETS OF PLANS. PLEASE SUBMIT COMPLETE SETS SECURED |
| | TOGETHER. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO, PLEASE SEE THE RESPONSE WAS TO ADD AND |
| | ADDITIONAL SERVICE, HOWEVER AS THIS DOES NOT AT THIS |
| | TIME FALL UNDER THE EXCEPTIONS FOR 230.2 THIS AHJ IS |
| | NOT ABLE TO GRANT THE ADDITIONAL SERVICE BEING |
| | PROPOSED. |
| | PLEASE PROVIDE THE LOADS ON THE EXISTING SERVICE ALONG |
| | WITH THE NEW LOADS. PLEASE KNOW THAT FURTHER |
| | INFORMATION WOULD BE NEEDED FOR ANY OTHER |
| | CONSIDERATION. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE LOADS ON EXISTING SERVICE GUTTER WITH |
| | NEW LOADS BEING ADDED. PLEASE ALSO INDICATE THE SIZE OF |
| | THE EXISTING SERVICE. |
| | 230.2, 220, 215.5 ETC |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: NO? THIS COMMENT IS CURRENTLY *UP IN THE AIR* |
| | BASED ON THE FACT THAT THE SERVICE RISER HAS NOW |
| | COMPLETELY CHANGED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR FROM |
| | GUTTER TO METER, METER TO MAIN, MAIN TO SUB PANEL, |
| | PANELS TO TRANSFORMERS, AND TRANSFORMER TO PANELS. ** |
| | PLEASE KNOW, IF MAIN SERVICE FOR BUILDING CONTAINS AS |
| | MAIN, THEN PROVIDE NOTE ON PLANS FOR "FLOATING NEUTRAL" |
| | KIT REQUIRED IN METER. |
| | 250.6, 250.24B, 250.110,250.6,250.122 ETC. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK, THE LOCATIONS ARE NOW BEING SHOWN, HOWEVER |
| | THE MINIMUM CLEARANCES FOR WORKING CLEARANCE, |
| | VENTILATION AND POSSIBLE STORAGE AREA THESE ARE BEING |
| | SHOWN IS NOT CLEAR. |
| | PLEASE SEEDISCONNECT AS SHOWN ON PLANS ALSO DOES NOT |
| | MEET MINIMUM CLEARANCE REQUIREMENTS.PLEASE SEE 110.26 |
| | AND THE SAME CODE SECTIONS AS PREVIOUSLY NOTED. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW LOCATIONS OF TRANSFORMERS ON PLANS. PLEASE |
| | SEE THAT A REVIEW FOR SOME CODE ITEMS CAN NOT BE DONE |
| | AT THIS TIME AS THESE ARE NOT SHOWN. |
| | PLEASE SEE INSTALLATION OF THE 112.5KVA TRANSFORMER |
| | SHALL NOT BE ABOVE CEILING AND MUST MEET ALL THE |
| | REQUIREMENTS AS |
| | NEC ARTICLES BELOW REQUIRE. |
| | PLEASE SEE 450.13B, 450.21, 450.9 ETC. |
| | ** IF TRANSFORMER(S) ARE GOING TO BE MOUNTED FROM |
| | CEILING OR WALL, PLEASE PROVIDE STRUCTURAL ENGINEERING |
| | DETAILS FOR THIS. |
| | |
| | 7) NOTE: NO, PLEASE SEE THE TAPPED CONDUCTORS DO NOT |
| | SEEM TO MEET THE CODE SECTION AS PREVIOUSLY GIVEN. |
| | PLEASE SEE 240.21C6. PLEASE SEE THE DISTANCE ALONG WITH |
| | THE SIZE OF THE CONDUCTOR TERMINATING INTO OVER CURRENT |
| | PROTECTION WHICH LIMITS THE LOAD ON ANY CONDUCTOR IS |
| | NOT MET AT THIS TIME. |
| | PLEASE SEE THE RISER INDICATES 400AMP OCP ON |
| | CONDUCTORS RATED AT 285AMPS. |
| | |
| | **PREVIOUS REVIEW NOTE** |
| | PLEASE SEE 240.21 FOR TAPPED CONDUCTORS ON THE |
| | SECONDARY SIDE OF TRANSFORMERS CAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | |
| | 8) NOTE: OK, SEE NOTE ABOVE #7. |
| | |
| | 9) NOTE: NO/OK, PLEASE SEE THIS WAS NOT DONE, HOWEVER |
| | AS EQUIPMENT IS REMOVED FROM THE LIGHTING PLANS, IT |
| | NEED ONLY BE SHOWN ON THE POWER PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE ALL PLANS FOR LOCATIONS OF ALL SERVICE |
| | EQUIPMENT PANELS. PLEASE SEE PANELS ON LIGHTING SHEETS |
| | ARE NOT IN THE SAME LOCATIONS AS PANELS ON POWER |
| | SHEETS. |
| | 106.1.2.FBC 110.26,240.24 ETC. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE:NO, PLEASE SEE MOST WERE DONE, HOWEVER |
| | PLEASE SEE PLANS AS THERE ARE SOME FIXTURES BEING |
| | CIRCUITED TO CIRCUITS WHICH ARE SHOWN AS *BLANK* IN |
| | PANEL SCHEDULE. PLEASE SEE REDLINED PLANS AND PLEASE |
| | SEE NEW COMMENTS BASED ON COORDINATION OF CIRCUITING ON |
| | PLANS, PANEL SCHEDULE, ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LTS. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 15) NOTE:OK, HOWEVER PLEASE SEE THERMOSTATICALLY |
| | CONTROLLED DEVICES ARE NOW BEING SHOWN AT 125%? THIS IS |
| | OK AND IS ONLY BEING NOTED AS NOT REQUIRED. THE |
| | PREVIOUS NOTE IS BEING LEFT AS THE NOTE MENTIONS THIS |
| | WAS EXEMPT. PLEASE ALSO SEE NOTE AS THE LOADS WILL BE |
| | CONSIDERED FOR THE EXISTING MAIN SERVICE WHICH IS BEING |
| | CONNECTED TO. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PANEL SCHEDULES ARE NOT COMPLETE WITH LOAD |
| | CALCULATIONS AT THIS TIME. PLEASE PROVIDE COMPLETE LOAD |
| | CALCULATIONS ON HOW LOADS WERE DERIVED. |
| | PLEASE SEE 220.3,220.10,220.11,220.13 ETC |
| | PLEASE ALSO INDICATE AND SHOW ALL CONTINUOUS LOADS (3OR |
| | MORE HRS) AT 125%. (THERMOSTATICALLY CONTROLLED |
| | UNITS/APPLIANCES ARE IN EXCEPTION) |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE: OK. |
| | |
| | |
| | 18) NOTE: OK, THESE ARE BEING ADDED, HOWEVER PLEASE |
| | CLARIFY HOW LOAD WAS DERIVED. *EXAMPLE* X AMOUNT OF |
| | LINEAR FT OF WINDOW AT 200VA PER FT = Y* |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY NEW OR EXISTING SHOW/STOREFRONT WINDOW |
| | RECEPTS REQUIRED ABOVE WINDOWS.210.62 |
| | THESE WILL BE REQUIRED IF NOT EXISTING. |
| | PLEASE ALSO SEE 220.12 FOR LOADS TO BE ADJUSTED. |
| | |
| | 19) NOTE: OK. |
| | |
| | 20) NOTE: OK. |
| | |
| | 21) NOTE:NO, |
| | A) PLEASE SEE THE LIGHTING CONTROL PANEL DOES NOT |
| | CONTAIN ANY TIME OF DAY SCHEDULING. (EXAMPLE: 8AM |
| | -11PM). |
| | B) PLEASE SEE THE CIRCUITING ON PLANS DOES NOT |
| | CORRELATE WITH THE CIRCUITING ON PLANS OR PANEL |
| | SCHEDULE(S). |
| | C) PLEASE SEE THE METHOD *A* FOR LIGHTING CAN NOT BE |
| | VERIFIED AT THIS TIME. PLEASE SEE THAT THE ENERGY |
| | CALCULATIONS SUBMITTED DO NOT CORRELATE WITH THE |
| | LIGHTING ON PLANS OR LOADS SHOWN ON PLANS FOR LIGHTING. |
| | PLEASE CORRELATE. |
| | D) PLEASE SEE BATHROOMS AS THE COVERAGE OF THE DEVICE |
| | AS SHOWN WOULD NOT COVER THE OTHER CLOSED IN |
| | AREAS/STALLS OF RESTROOM AREAS. PLEASE SEE THE TYPE OF |
| | DEVICE MAY BE SPECIFIED WHICH MAY HELP IN COVERAGE; |
| | HOWEVER DEPENDING ON DEVICE, COVERAGE, WALLS/PARTITIONS |
| | ETC THESE WILL ALL HAVE AN AFFECT ON THE DESIGN FOR |
| | LIFE SAFETY OF THESE LIGHTS. |
| | ** THE INTENT IS NOT TO LEAVE AN OCCUPANT IN ANY AREA |
| | IN TOTAL DARKNESS IN THE EVENT OF THE FAILURE OR |
| | TURNING OFF OF THIS ONE DEVICE. |
| | PLEASE SEE NEW COMMENT BASED ON THE TYPE OF EMERGENCY |
| | FIXTURE BEING PLACED IN BATHROOM. |
| | |
| | ** PLEASE SEE THE PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THIS IS A NEW OCCUPANCY FOR SPACE. PLEASE |
| | SEE 2004 FBC CHAPTER 13 FOR COMPLIANCE WITH THE NEW |
| | FLORIDA ENERGY CODE. |
| | PLEASE SEE 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, AND |
| | 13-415.1.ABC.1.3 |
| | PLEASE PROVIDE A COMPLETE LIGHTING CONTROL SYSTEM AS |
| | REQUIRED INCLUDING CONTROLS AND DEVICES FOR ALL |
| | SEPARATE SPACES CONTAIN FLR TO CEILING HEIGHT |
| | PARTITIONS. |
| | PLEASE PROVIDE THE SCHEDULING; PLEASE PROVIDE TYPE OF |
| | OVER RIDE DEVICES, ALONG WITH THE MAX TIME OVER RIDE AS |
| | DETERMINED BY THE DEVICE. ( TIMER TYPE4HRS MAX, |
| | MOTION/OCCUPANT SENSOR TYPE 30MINS MAX). |
| | PLEASE SEE CONTROLS FOR OVER-RIDING SYSTEM SHALL ALSO |
| | BE LOCATED AT THE POINTS OF ENTRANCE INTO SPACE. PLEASE |
| | SEE THAT ANY OVER-RIDES MUST ALSO BE LOCATED SO THE |
| | OCCUPANT CAN VISUALLY SEE THE LIGHTING BEING |
| | CONTROLLED. |
| | PLEASE SUBMIT LIGHTING POWER DENSITIES AS REQUIREDPER |
| | 13-415.1.AB.1, |
| | 13-415.2.ABC.1, AND TABLES 415.2.C.1, |
| | 415.2.B.1, 13-415.2.B.1 ETC ETC. |
| | PLEASE PROVIDE THE MAX ALLOWED COMPARED TO THE ACTUAL |
| | DESIGN. |
| | PLEASE SEE METHODS FOR NEW ENERGY CALCULATIONS MUST |
| | ALSO BE SUBMITTED. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE: OK. |
| | |
| | ** NEW NOTES ** |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING FIXTURE SCHEDULE. |
| | PLEASE SOME FIXTURES WHICH ARE BEING SHOWN AS |
| | EMERGENCY, HOWEVER THEY DO NOT CONTAIN ANY BATTERY BACK |
| | UP. PLEASE SEE THE BATHROOMS ARE ONE LOCATION AS NOTED |
| | ABOVE WHERE AN EMERGENCY BATTERY BACK UP LIGHT FIXTURE |
| | OF SOME SORT IS REQUIRED. |
| | NFPA-101 7.8, 7.9. |
| | 700.12 E, 700.16 NEC. |
| | |
| | 2) NOTE:PLEASE SEE ARCHITECTURAL COVER SHEET MENTIONS |
| | THIS AS LEVEL 2 ALTERATION FROM THE EXISTING 2004 FBC. |
| | THIS IS NOT POSSIBLE FOR A CHANGE IN OCCUPANCY OR THE |
| | SCOPE OF WORK IN THIS PROJECT. PLEASE ALSO SEE BUIDLING |
| | REVIEW COMMENTS FOR THIS. |
| | |
| | 3) NOTE: PLEASE SEE FS 553.80(2)(B) WHICH IS BEING |
| | GIVEN AS A NOTICE ONLY AT THIS TIME. |
| | |
| | ** PLEASE KNOW, AS THERE ARE ITEMS NOT |
| | YET SUBMITTED FOR REVIEW, THERE MAY BE |
| | NEW COMMENTS UPON NEXT REVIEW. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |