Plan Review Notes
Plan Review Notes For Permit 06081940
Permit Number 06081940
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-24 12:38:41***** UNSAT 2ND REVIEW *****
  
 ITALIAN OVEN
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO DO NOT SUBMIT LOOSE SHEETS NOT ATTACHED IN
 THE SETS OF PLANS. PLEASE SUBMIT COMPLETE SETS SECURED
 TOGETHER.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THE RESPONSE WAS TO ADD AND
 ADDITIONAL SERVICE, HOWEVER AS THIS DOES NOT AT THIS
 TIME FALL UNDER THE EXCEPTIONS FOR 230.2 THIS AHJ IS
 NOT ABLE TO GRANT THE ADDITIONAL SERVICE BEING
 PROPOSED.
 PLEASE PROVIDE THE LOADS ON THE EXISTING SERVICE ALONG
 WITH THE NEW LOADS. PLEASE KNOW THAT FURTHER
 INFORMATION WOULD BE NEEDED FOR ANY OTHER
 CONSIDERATION.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE LOADS ON EXISTING SERVICE GUTTER WITH
 NEW LOADS BEING ADDED. PLEASE ALSO INDICATE THE SIZE OF
 THE EXISTING SERVICE.
 230.2, 220, 215.5 ETC
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: NO? THIS COMMENT IS CURRENTLY *UP IN THE AIR*
 BASED ON THE FACT THAT THE SERVICE RISER HAS NOW
 COMPLETELY CHANGED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR FROM
 GUTTER TO METER, METER TO MAIN, MAIN TO SUB PANEL,
 PANELS TO TRANSFORMERS, AND TRANSFORMER TO PANELS. **
 PLEASE KNOW, IF MAIN SERVICE FOR BUILDING CONTAINS AS
 MAIN, THEN PROVIDE NOTE ON PLANS FOR "FLOATING NEUTRAL"
 KIT REQUIRED IN METER.
 250.6, 250.24B, 250.110,250.6,250.122 ETC.
  
 5) NOTE: OK.
  
 6) NOTE: OK, THE LOCATIONS ARE NOW BEING SHOWN, HOWEVER
 THE MINIMUM CLEARANCES FOR WORKING CLEARANCE,
 VENTILATION AND POSSIBLE STORAGE AREA THESE ARE BEING
 SHOWN IS NOT CLEAR.
 PLEASE SEEDISCONNECT AS SHOWN ON PLANS ALSO DOES NOT
 MEET MINIMUM CLEARANCE REQUIREMENTS.PLEASE SEE 110.26
 AND THE SAME CODE SECTIONS AS PREVIOUSLY NOTED.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW LOCATIONS OF TRANSFORMERS ON PLANS. PLEASE
 SEE THAT A REVIEW FOR SOME CODE ITEMS CAN NOT BE DONE
 AT THIS TIME AS THESE ARE NOT SHOWN.
 PLEASE SEE INSTALLATION OF THE 112.5KVA TRANSFORMER
 SHALL NOT BE ABOVE CEILING AND MUST MEET ALL THE
 REQUIREMENTS AS
 NEC ARTICLES BELOW REQUIRE.
 PLEASE SEE 450.13B, 450.21, 450.9 ETC.
 ** IF TRANSFORMER(S) ARE GOING TO BE MOUNTED FROM
 CEILING OR WALL, PLEASE PROVIDE STRUCTURAL ENGINEERING
 DETAILS FOR THIS.
  
 7) NOTE: NO, PLEASE SEE THE TAPPED CONDUCTORS DO NOT
 SEEM TO MEET THE CODE SECTION AS PREVIOUSLY GIVEN.
 PLEASE SEE 240.21C6. PLEASE SEE THE DISTANCE ALONG WITH
 THE SIZE OF THE CONDUCTOR TERMINATING INTO OVER CURRENT
 PROTECTION WHICH LIMITS THE LOAD ON ANY CONDUCTOR IS
 NOT MET AT THIS TIME.
 PLEASE SEE THE RISER INDICATES 400AMP OCP ON
 CONDUCTORS RATED AT 285AMPS.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE 240.21 FOR TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF TRANSFORMERS CAN NOT BE VERIFIED AT
 THIS TIME.
  
 8) NOTE: OK, SEE NOTE ABOVE #7.
  
 9) NOTE: NO/OK, PLEASE SEE THIS WAS NOT DONE, HOWEVER
 AS EQUIPMENT IS REMOVED FROM THE LIGHTING PLANS, IT
 NEED ONLY BE SHOWN ON THE POWER PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ALL PLANS FOR LOCATIONS OF ALL SERVICE
 EQUIPMENT PANELS. PLEASE SEE PANELS ON LIGHTING SHEETS
 ARE NOT IN THE SAME LOCATIONS AS PANELS ON POWER
 SHEETS.
 106.1.2.FBC 110.26,240.24 ETC.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE:NO, PLEASE SEE MOST WERE DONE, HOWEVER
 PLEASE SEE PLANS AS THERE ARE SOME FIXTURES BEING
 CIRCUITED TO CIRCUITS WHICH ARE SHOWN AS *BLANK* IN
 PANEL SCHEDULE. PLEASE SEE REDLINED PLANS AND PLEASE
 SEE NEW COMMENTS BASED ON COORDINATION OF CIRCUITING ON
 PLANS, PANEL SCHEDULE, ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 15) NOTE:OK, HOWEVER PLEASE SEE THERMOSTATICALLY
 CONTROLLED DEVICES ARE NOW BEING SHOWN AT 125%? THIS IS
 OK AND IS ONLY BEING NOTED AS NOT REQUIRED. THE
 PREVIOUS NOTE IS BEING LEFT AS THE NOTE MENTIONS THIS
 WAS EXEMPT. PLEASE ALSO SEE NOTE AS THE LOADS WILL BE
 CONSIDERED FOR THE EXISTING MAIN SERVICE WHICH IS BEING
 CONNECTED TO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULES ARE NOT COMPLETE WITH LOAD
 CALCULATIONS AT THIS TIME. PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONS ON HOW LOADS WERE DERIVED.
 PLEASE SEE 220.3,220.10,220.11,220.13 ETC
 PLEASE ALSO INDICATE AND SHOW ALL CONTINUOUS LOADS (3OR
 MORE HRS) AT 125%. (THERMOSTATICALLY CONTROLLED
 UNITS/APPLIANCES ARE IN EXCEPTION)
  
 16) NOTE: OK.
  
 17) NOTE: OK.
  
  
 18) NOTE: OK, THESE ARE BEING ADDED, HOWEVER PLEASE
 CLARIFY HOW LOAD WAS DERIVED. *EXAMPLE* X AMOUNT OF
 LINEAR FT OF WINDOW AT 200VA PER FT = Y*
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY NEW OR EXISTING SHOW/STOREFRONT WINDOW
 RECEPTS REQUIRED ABOVE WINDOWS.210.62
 THESE WILL BE REQUIRED IF NOT EXISTING.
 PLEASE ALSO SEE 220.12 FOR LOADS TO BE ADJUSTED.
  
 19) NOTE: OK.
  
 20) NOTE: OK.
  
 21) NOTE:NO,
 A) PLEASE SEE THE LIGHTING CONTROL PANEL DOES NOT
 CONTAIN ANY TIME OF DAY SCHEDULING. (EXAMPLE: 8AM
 -11PM).
 B) PLEASE SEE THE CIRCUITING ON PLANS DOES NOT
 CORRELATE WITH THE CIRCUITING ON PLANS OR PANEL
 SCHEDULE(S).
 C) PLEASE SEE THE METHOD *A* FOR LIGHTING CAN NOT BE
 VERIFIED AT THIS TIME. PLEASE SEE THAT THE ENERGY
 CALCULATIONS SUBMITTED DO NOT CORRELATE WITH THE
 LIGHTING ON PLANS OR LOADS SHOWN ON PLANS FOR LIGHTING.
 PLEASE CORRELATE.
 D) PLEASE SEE BATHROOMS AS THE COVERAGE OF THE DEVICE
 AS SHOWN WOULD NOT COVER THE OTHER CLOSED IN
 AREAS/STALLS OF RESTROOM AREAS. PLEASE SEE THE TYPE OF
 DEVICE MAY BE SPECIFIED WHICH MAY HELP IN COVERAGE;
 HOWEVER DEPENDING ON DEVICE, COVERAGE, WALLS/PARTITIONS
 ETC THESE WILL ALL HAVE AN AFFECT ON THE DESIGN FOR
 LIFE SAFETY OF THESE LIGHTS.
 ** THE INTENT IS NOT TO LEAVE AN OCCUPANT IN ANY AREA
 IN TOTAL DARKNESS IN THE EVENT OF THE FAILURE OR
 TURNING OFF OF THIS ONE DEVICE.
 PLEASE SEE NEW COMMENT BASED ON THE TYPE OF EMERGENCY
 FIXTURE BEING PLACED IN BATHROOM.
  
 ** PLEASE SEE THE PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS IS A NEW OCCUPANCY FOR SPACE. PLEASE
 SEE 2004 FBC CHAPTER 13 FOR COMPLIANCE WITH THE NEW
 FLORIDA ENERGY CODE.
 PLEASE SEE 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, AND
 13-415.1.ABC.1.3
 PLEASE PROVIDE A COMPLETE LIGHTING CONTROL SYSTEM AS
 REQUIRED INCLUDING CONTROLS AND DEVICES FOR ALL
 SEPARATE SPACES CONTAIN FLR TO CEILING HEIGHT
 PARTITIONS.
 PLEASE PROVIDE THE SCHEDULING; PLEASE PROVIDE TYPE OF
 OVER RIDE DEVICES, ALONG WITH THE MAX TIME OVER RIDE AS
 DETERMINED BY THE DEVICE. ( TIMER TYPE4HRS MAX,
 MOTION/OCCUPANT SENSOR TYPE 30MINS MAX).
 PLEASE SEE CONTROLS FOR OVER-RIDING SYSTEM SHALL ALSO
 BE LOCATED AT THE POINTS OF ENTRANCE INTO SPACE. PLEASE
 SEE THAT ANY OVER-RIDES MUST ALSO BE LOCATED SO THE
 OCCUPANT CAN VISUALLY SEE THE LIGHTING BEING
 CONTROLLED.
 PLEASE SUBMIT LIGHTING POWER DENSITIES AS REQUIREDPER
 13-415.1.AB.1,
 13-415.2.ABC.1, AND TABLES 415.2.C.1,
 415.2.B.1, 13-415.2.B.1 ETC ETC.
 PLEASE PROVIDE THE MAX ALLOWED COMPARED TO THE ACTUAL
 DESIGN.
 PLEASE SEE METHODS FOR NEW ENERGY CALCULATIONS MUST
 ALSO BE SUBMITTED.
  
 22) NOTE: OK.
  
 23) NOTE: OK.
  
 ** NEW NOTES **
  
 1) NOTE: PLEASE SEE THE LIGHTING FIXTURE SCHEDULE.
 PLEASE SOME FIXTURES WHICH ARE BEING SHOWN AS
 EMERGENCY, HOWEVER THEY DO NOT CONTAIN ANY BATTERY BACK
 UP. PLEASE SEE THE BATHROOMS ARE ONE LOCATION AS NOTED
 ABOVE WHERE AN EMERGENCY BATTERY BACK UP LIGHT FIXTURE
 OF SOME SORT IS REQUIRED.
 NFPA-101 7.8, 7.9.
 700.12 E, 700.16 NEC.
  
 2) NOTE:PLEASE SEE ARCHITECTURAL COVER SHEET MENTIONS
 THIS AS LEVEL 2 ALTERATION FROM THE EXISTING 2004 FBC.
 THIS IS NOT POSSIBLE FOR A CHANGE IN OCCUPANCY OR THE
 SCOPE OF WORK IN THIS PROJECT. PLEASE ALSO SEE BUIDLING
 REVIEW COMMENTS FOR THIS.
  
 3) NOTE: PLEASE SEE FS 553.80(2)(B) WHICH IS BEING
 GIVEN AS A NOTICE ONLY AT THIS TIME.
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 YET SUBMITTED FOR REVIEW, THERE MAY BE
 NEW COMMENTS UPON NEXT REVIEW.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]