Plan Review Notes
Plan Review Notes For Permit 06081940
Permit Number 06081940
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-08 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS SHALL BE ROUTED TO DBPR
 RESTURANT AND HOTEL DIVISION FOR REVIEW
 PRIOR TO RESUBMITTING. PLANS SHALL BE
 STAMPED AND TWO PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS TO BE
 SUBMITTED. SECTION 102.2.1
  
 2. SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE REQUIREMENTS. TABLES 1004.1.2
 AND 403.1.
  
 3. SUBMIT AN EXISTING FLOOR PLAN TO
 DETERMINE THE EXTENT OF THE DEMO WORK TO
 BE DONE. SECTION 106.1.1.
  
 4. GREASE INTERCEPTOR SHALL BE SIZED BY
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT LYNN BY PHONE (561)
 822-2271, OR BY FAX (561) 822-2279, OR
 E-MAIL [email protected]. MUNICIPAL CODE
 SECTION 3434.
  
 5. SHT A1.1 EQUIPMENT LIST INDICATES TWO
 #19 HAND SINKS, BUT ONLY ONE WAS FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT P-0 PLUMBING SPECIFICATIONS.
 FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. FLOOR SINKS OR
 HUB DRAINS SHALL BE USED. SECTIONS 802.3
 AND 802.3.2.
  
 7. SHT P-3 DOMESTIC WATER ISOMETRIC.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES, IN AN "EFFECTIVE
 RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 8. SHT P-3 THE FOLLOWING INFORMATION IS
 REQUIRED FOR REQUIRED GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGTHS NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. UNION NOT
 SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]