| 2006-09-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. PLANS SHALL BE ROUTED TO DBPR |
| | RESTURANT AND HOTEL DIVISION FOR REVIEW |
| | PRIOR TO RESUBMITTING. PLANS SHALL BE |
| | STAMPED AND TWO PAGE "WORKSHEETS" |
| | ATTACHED TO EACH SET OF PLANS TO BE |
| | SUBMITTED. SECTION 102.2.1 |
| | |
| | 2. SUBMIT CALCULATIONS FOR MINIMUM |
| | FIXTURE REQUIREMENTS. TABLES 1004.1.2 |
| | AND 403.1. |
| | |
| | 3. SUBMIT AN EXISTING FLOOR PLAN TO |
| | DETERMINE THE EXTENT OF THE DEMO WORK TO |
| | BE DONE. SECTION 106.1.1. |
| | |
| | 4. GREASE INTERCEPTOR SHALL BE SIZED BY |
| | LYNN MASSON, ENVIRONMENTAL COMPLIANCE |
| | MANAGER. CONTACT LYNN BY PHONE (561) |
| | 822-2271, OR BY FAX (561) 822-2279, OR |
| | E-MAIL [email protected]. MUNICIPAL CODE |
| | SECTION 3434. |
| | |
| | 5. SHT A1.1 EQUIPMENT LIST INDICATES TWO |
| | #19 HAND SINKS, BUT ONLY ONE WAS FOUND. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 6. SHT P-0 PLUMBING SPECIFICATIONS. |
| | FLOOR DRAINS ARE NOT AN APPROVED |
| | INDIRECT WASTE RECEPTOR. FLOOR SINKS OR |
| | HUB DRAINS SHALL BE USED. SECTIONS 802.3 |
| | AND 802.3.2. |
| | |
| | 7. SHT P-3 DOMESTIC WATER ISOMETRIC. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES, IN AN "EFFECTIVE |
| | RANGE", NOT IN THE CEILING AS SHOWN. |
| | PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 8. SHT P-3 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR REQUIRED GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. LENGTHS NOT SHOWN. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | E. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | F. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. UNION NOT |
| | SHOWN. |
| | |