| 2006-10-11 19:01:58 | ------------------DENIED------------------------- |
| | |
| | 1. EXISTING AHU 1 ACCESS MUST BE LARGE ENOUGH FOR |
| | REPLACEMENT OF EQUIPMENT PER FBC,M 306 |
| | |
| | 2. KSF 1 REQUIRES DUCT MOUNTED SMOKE DETECTOR AS IT |
| | EXCEEDS 2,000 CFM.ALL DUCT DETECTORS ARE TO BE TIED |
| | IN TO THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606 |
| | |
| | 3. VERIFY KSF 1 INTAKE IS IN COMPLIANCE WITH FBC,M |
| | 401.5.1 |
| | |
| | 4. PROVIDE DETAIL FOR GREASE EXHAUST DUCT PENETRATIONS |
| | THROUGH RATED WALLS AND SHAFTS. SHOW COMPLIANCE WITH |
| | FBC,M 506.3.10 WITH 2 HOUR LISTED SYSTEMS TO BE USED |
| | AND INSTALLATION INSTRUCTIONS. |
| | |
| | 5. HORIZONTAL GREASE EXHAUST DUCT THROUGH LOBBY FOR |
| | LOFTS REQUIRES CLEAN OUTS PER 506.3.9. HOW WILL ASSESS |
| | TO CLEAN-OUTS BE PROVIDED IN LOBBY AREA? |
| | |
| | 6. PAGE M3: A/C ROOF EQUIPMENT MOUNTING DETAIL NOTE |
| | REFERS TO FBC 2001. PLEASE REFERENCE FBC 2004. |
| | |
| | 7. PAGE M4: BALANCING GREASE EXHAUST DAMPER DETAIL - IS |
| | THERE TO BE A BALANCING DAMPER INSIDE THE GREASE |
| | EXHAUST DUCT? IS THERE A GAP BETWEEN THE HOOD COLLAR |
| | AND THE DUCT? PLEASE CLARIFY. |
| | |
| | 8. SEPERATE PERMITS ARE REQUIRED FOR A/C, HOOD SYSTEMS, |
| | HOOD SUPPRESSION SYSTEMS, WALK-IN COOLERS/FREEZERS. |
| | ONLY THE A/C AND GREASE EXHAUST DUCT SYSTEMS WERE |
| | REVIEWED FOR CODE COMPLIANCE. APPLICATIONS AND |
| | SUBMITTALS FOR ALL OTHER SYSTEMS WILL BE REQUIRED PRIOR |
| | TO ISSUANCE OF EACH PERMIT. |
| | |