2006-10-11 19:01:58------------------DENIED-------------------------
  
 1. EXISTING AHU 1 ACCESS MUST BE LARGE ENOUGH FOR
 REPLACEMENT OF EQUIPMENT PER FBC,M 306
  
 2. KSF 1 REQUIRES DUCT MOUNTED SMOKE DETECTOR AS IT
 EXCEEDS 2,000 CFM.ALL DUCT DETECTORS ARE TO BE TIED
 IN TO THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606
  
 3. VERIFY KSF 1 INTAKE IS IN COMPLIANCE WITH FBC,M
 401.5.1
  
 4. PROVIDE DETAIL FOR GREASE EXHAUST DUCT PENETRATIONS
 THROUGH RATED WALLS AND SHAFTS. SHOW COMPLIANCE WITH
 FBC,M 506.3.10 WITH 2 HOUR LISTED SYSTEMS TO BE USED
 AND INSTALLATION INSTRUCTIONS.
  
 5. HORIZONTAL GREASE EXHAUST DUCT THROUGH LOBBY FOR
 LOFTS REQUIRES CLEAN OUTS PER 506.3.9. HOW WILL ASSESS
 TO CLEAN-OUTS BE PROVIDED IN LOBBY AREA?
  
 6. PAGE M3: A/C ROOF EQUIPMENT MOUNTING DETAIL NOTE
 REFERS TO FBC 2001. PLEASE REFERENCE FBC 2004.
  
 7. PAGE M4: BALANCING GREASE EXHAUST DAMPER DETAIL - IS
 THERE TO BE A BALANCING DAMPER INSIDE THE GREASE
 EXHAUST DUCT? IS THERE A GAP BETWEEN THE HOOD COLLAR
 AND THE DUCT? PLEASE CLARIFY.
  
 8. SEPERATE PERMITS ARE REQUIRED FOR A/C, HOOD SYSTEMS,
 HOOD SUPPRESSION SYSTEMS, WALK-IN COOLERS/FREEZERS.
 ONLY THE A/C AND GREASE EXHAUST DUCT SYSTEMS WERE
 REVIEWED FOR CODE COMPLIANCE. APPLICATIONS AND
 SUBMITTALS FOR ALL OTHER SYSTEMS WILL BE REQUIRED PRIOR
 TO ISSUANCE OF EACH PERMIT.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]