Plan Review Notes
Plan Review Notes For Permit 06081940
Permit Number 06081940
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-12 13:08:25*****UNSAT*****
  
  
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE , 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST
 DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 04.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 05.)ON THE APPROPIATE STOREFRONT AND (OR) ELEVATION
 SHEET, SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 STRUCTURE.AS PER WEST PALM BEACH CODE, THE CHARACTERS
 (NUMBERS AND/OR LETTERS) SHALL BE NO LESS THAN 6" IN
 HEIGHT AND 1" IN WIDTH.IF SO EQUIPPED, HURRICANE
 SHUTTERS SHALL NOT COVER OR CONCEAL THE ADDRESS.
  
 06.)WHERE THE BUILDING IS PROTECTED BY FIRE
 PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING ALTERATION.
  
 07.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED
 FOR REVIEW.
  
 08.)PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS, AND FIRE
 PROTECTION SYSTEM(S).HOW WILL THEY BE AFFECTED BY THE
 SCOPE OF WORK?
  
 09.)ADDITIONAL PERMIT AND PLANS REQUIRED FOR
 MECHANICAL HOOD/SUPPRESSION SYSTEM.
  
 10.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 8561-805-6722