Plan Review Notes
Plan Review Notes For Permit 06081940
Permit Number 06081940
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-09 00:00:00***** UNSAT *****
  
 ITALIAN OVEN
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES
 ARE REQUIRED ON PLANS WHICH ARE RELEVANT
 TO THE SCOPE OF WORK AND DESIGNS ON
 PLANS.
 2004 FBC, 2002 NFPA-70 (NEC), 2002
 NFPA-72. 2004 NFPA-96, 2003 NFPA-101.
 THESE ARE REQUIRED AT A MIN.
  
 2) NOTE: PLEASE SEE ADDRESS OF SUITE
 SHALL BE INDICATED ON TITLE BLOCKS ARE
 REQUIRED UNDER THE FLORIDA
 ADMINISTRATIVE CODE.
 61G1-16.004 AND 61G15-23.002
 PLEASE BE SURE TO ALSO CORRELATE WITH
 THE PERMIT APPLICATION AS NO SUITE
 NUMBER IS SHOWN.
  
 3) NOTE: PLEASE PROVIDE LOADS ON
 EXISTING SERVICE GUTTER WITH NEW LOADS
 BEING ADDED. PLEASE ALSO INDICATE THE
 SIZE OF THE EXISTING SERVICE.
 230.2, 220, 215.5 ETC
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM GUTTER TO
 METER, METER TO MAIN, MAIN TO SUB PANEL,
 PANELS TO TRANSFORMERS, AND TRANSFORMER
 TO PANELS.
 ** PLEASE KNOW, IF MAIN SERVICE FOR
 BUILDING CONTAINS AS MAIN , THEN PROVIDE
 NOTE ON PLANSFOR "FLOATING NEUTRAL"
 KIT REQUIRED IN METER.
 250.6,250.24B, 250.110,250.6,250.122
 ETC.
  
 5) NOTE: PLEASE SHOW AND INDICATE THE
 GROUNDING ATTACHMENT LOCATIONS FOR NEW
 AND EXISTING TRANSFORMERS.
 PLEASE SEE 250.30,250.20,250.66, 250.58,
 250.50
  
 6) NOTE: PLEASE SHOW LOCATIONS OF
 TRANSFORMERS ON PLANS. PLEASE SEE THAT A
 REVIEW FOR SOME CODE ITEMS CAN NOT BE
 DONE AT THIS TIME AS THESE ARE NOT
 SHOWN.
 PLEASE SEE INSTALLATION OF THE 112.5KVA TRANSFORMER
 SHALL NOT BE ABOVE CEILING
 AND MUST MEET ALL THE REQUIREMENTS AS
 NEC ARTICLES BELOW REQUIRE.
 PLEASE SEE 450.13B, 450.21, 450.9 ETC.
 ** IF TRANSFORMER(S) ARE GOING TO BE
 MOUNTED FROM CEILING OR WALL, PLEASE
 PROVIDE STRUCTURAL ENGINEERING DETAILS
 FOR THIS.
  
 7) NOTE: PLEASE SEE 240.21 FOR TAPPED
 CONDUCTORS ON THE SECONDARY SIDE OF
 TRANSFORMERS CAN NOT BE VERIFIED AT THIS
 TIME.
  
 8) NOTE: PLEASE SEE PANEL LPH AND LP/LP
 SHOULD BE SHOWN AS 400A RATED AND
 CONTAINING A 300A BRKR IF THIS IS GOING
 TO BE THE DESIGN. PLEASE SEE PANEL NOW
 SHOWS A 400A BRKR WITH A 300A TRIP?
 IF THIS TYPE OF BRKR IS GOING TOBE
 INSTALLED, PLEASE SUBMIT MANUFACTURES
 CUT/SPEC SHEETS ON THIS BREAKER, MUST
 INDICATE A LISTING FROM A NRTL.
 110.3,90.7.
  
 9) NOTE: PLEASE CORRELATE ALL PLANS FOR
 LOCATIONS OF ALL SERVICE EQUIPMENT
 PANELS. PLEASE SEE PANELS ON LIGHTING
 SHEETS ARE NOT IN THE SAME LOCATIONS AS
 PANELS ON POWER SHEETS.
 106.1.2.FBC
 110.26,240.24 ETC.
  
 10) NOTE: PLEASE CORRELATE RISER AND
 PANELS FOR FEEDER SIZES.
 310.16 , 240.4
 PLEASE SEE NEW TRANSFORMER SHOWS 2/0'S
 ON PANEL AND RISER SHOWS 1/0'S. PLEASE
 SEE 310.16 AS THE 1/0'S AS SHOWN ARE
 NOTE RATED FOR OCP BEING PROVIDED.
  
 11) NOTE: PLEASE SEE 240.6 FOR SIZING OF
 STANDARDOCP DEVICES. PLEASE SEE 170A
 BRKR BEING SHOWN FOR THE NEW TRANSFORMER
 WHICH DOES NOT CORRELATE TO ANY OF THE
 STANDARDS.
 240.4, 310.16, 240.6, 450.3
  
 12) NOTE: PLEASE CORRELATE RISER AND
 PANEL SCHEDULES FOR LABELING OF PANELS.
 ( TWO LP1'S)
 FBC 106.1.2
  
 13) NOTE: PLEASE INDICATE THE NEW OR
 EXISTING SIGN CIRCUIT(S). AS REQUIRED
 PER 600.5 PLEASE SEE THAT EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL
 OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH
 CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 14) NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EMERGENCY AND EXIT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 15) NOTE: PLEASE SEE PANEL SCHEDULES ARE
 NOT COMPLETE WITH LOAD CALCULATIONS AT
 THIS TIME. PLEASE PROVIDE COMPLETE LOAD CALCULATIONS ON
 HOW LOADS WERE DERIVED.
 PLEASE SEE 220.3,220.10,220.11,220.13
 ETC
 PLEASE ALSO INDICATE AND SHOW ALL
 CONTINUOUS LOADS (3OR MORE HRS) AT 125%.
 (THERMOSTATICALLY CONTROLLED
 UNITS/APPLIANCES ARE IN EXCEPTION)
  
 16) NOTE: PLEASE SEE TRANSFORMER ARE
 BEING SHOWN WITH WHAT APPEARS TO BE
 "NEUTRALS" IN THE FEEDER CONDUITS GOING
 TO THE TRANSFORMERS? PLEASE KNOW, AS THE TRANSFORMERS
 ARE CONSIDERED SEPARATELY
 DERIVED SYSTEMS/SERVICES, A NEUTRAL
 CONDUCTOR IS NOT INSTALLED.
 PLEASE KEEP IN MIND THE PREVIOUS COMMENT
 ABOVE WHICH PREVIOUSLY MENTIONED MISSING
 EQUIPMENT GROUNDING CONDUCTORS.
  
 17) NOTE: PLEASE SEE2002 NEC, 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 18) NOTE: PLEASE VERIFY NEW OR EXISTING SHOW/STOREFRONT
 WINDOW RECEPTS REQUIRED
 ABOVE WINDOWS.210.62
 THESE WILL BE REQUIRED IF NOT EXISTING.
 PLEASE ALSO SEE 220.12 FOR LOADS TO BE
 ADJUSTED.
  
 19) NOTE: PLEASE SEE COLOR CODING FOR
 120/240V SYSTEM WIRING IS BEING SHOWN ON
 E-0, HOWEVER PLEASE SEE SYSTEM VOLTAGES
 ON PLANS ARE 120/208 AND 277/480V.
 PLEASE SEE COLOR CODING SHALL BE AS
 FOLLOWS.
 120/208,
 BLACK ,RED, BLUE
 &
 277/480V
 BROWN, PURPLE , YELLOW.
 PLEASE KNOW, "ORANGE" IS ONLY IDENTIFIED
 IN THE NEC FOR THE HIGH-LEG OF A OPEN
 DELTA SYSTEM, 120/240V.
 PLEASE ADJUST, 90.4
 ** ALL EXISTING SYSTEMS AT THIS LOCATION
 AT CITY PLACE AND THIS JURISDICATION ARE
 COLOR CODED THIS WAY.
  
 20) NOTE: PLEASE SEE MISSING SHUNT TRIP IDENTIFICATIONS
 FOR ALL ELECTRICAL
 FEEDING OR UNDER HOOD. LTS ETC).
 PLEASE SEE NFPA 2004/1998 BOTH ARE THE
 SAME FOR REQUIRED AUTOMATIC SHUNT UPON
 ACTIVATION OF ANY SURPRESSION SYSTEM.
  
 21) NOTE: PLEASE SEE THIS IS A NEW
 OCCUPANCY FOR SPACE. PLEASE SEE 2004 FBC
 CHAPTER 13 FOR COMPLIANCE WITH THE NEW
 FLORIDA ENERGY CODE.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, AND 13-415.1.ABC.1.3
 PLEASE PROVIDE A COMPLETE LIGHTING
 CONTROL SYSTEM AS REQUIRED INCLUDING
 CONTROLS AND DEVICES FOR ALL SEPARATE
 SPACES CONTAIN FLR TO CEILING HEIGHT
 PARTITIONS.
 PLEASE PROVIDE THE SCHEDULING, PLEASE
 PROVIDE TYPE OF OVER RIDE DEVICES, ALONG
 WITH THE NAX TIME OVE OVER RIDE AS
 DETERMINED BY THE DEVICE. ( TIMER TYPE
 4HRS MAX, MOTION/OCCUPANT SENSOR TYPE
 30MINS MAX).
 PLEASE SEE CONTROLS FOR OVER-RIDING
 SYSTEM SHALL ALSO BE LOCATED AT THE
 POINTS OF ENTRANCE INTO SPACE. PLEASE
 SEE THAT ANY OVER-RIDES MUST ALSO BE
 LOCATED SO THE OCCUPANT CAN VISUALLY SEE
 THE LIGTHING BEING CONTROLLED.
 PLEASE SUBMIT LIGHTING POWER DENSITES AS
 REQUIREDPER 13-415.1.AB.1,
 13-415.2.ABC.1, AND TABLES 415.2.C.1,
 415.2.B.1., 13-415.2.B.1 ETC ETC.
 PLEASE PROVIDE THE MAX ALLOWED COMPARED
 TO THE ACTUAL DESIGN.
 PLEASE SEE METHODS FOR NEW ENERGY
 CALCULATIONS MUST ALSO BE SUBMITTED.
  
 22) NOTE: PLEASE INDICATE IF "LP"
 CONTAINS FEED-THRU LUGS OR IS THERE OCP
 IN LP FEEDING 2ND SECTION OF LP.
  
 23) NOTE: PLEASE SEE 220.12,AN
 ADDITIONAL LOAD OF 150 VOLT-AMPERES
 SHALL BE INCLUDED FOR EVERY 600 MM (2
 FT) OF LIGHTING TRACK OR FRACTION
 THEREOF.
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 YET SUBMITTED FOR REVIEW, THERE MAY BE
 NEW COMMENTS UPON NEXT REVIEW.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved