| Date |
Text |
| 2006-09-09 00:00:00 | ***** UNSAT ***** |
| | |
| | ITALIAN OVEN |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES |
| | ARE REQUIRED ON PLANS WHICH ARE RELEVANT |
| | TO THE SCOPE OF WORK AND DESIGNS ON |
| | PLANS. |
| | 2004 FBC, 2002 NFPA-70 (NEC), 2002 |
| | NFPA-72. 2004 NFPA-96, 2003 NFPA-101. |
| | THESE ARE REQUIRED AT A MIN. |
| | |
| | 2) NOTE: PLEASE SEE ADDRESS OF SUITE |
| | SHALL BE INDICATED ON TITLE BLOCKS ARE |
| | REQUIRED UNDER THE FLORIDA |
| | ADMINISTRATIVE CODE. |
| | 61G1-16.004 AND 61G15-23.002 |
| | PLEASE BE SURE TO ALSO CORRELATE WITH |
| | THE PERMIT APPLICATION AS NO SUITE |
| | NUMBER IS SHOWN. |
| | |
| | 3) NOTE: PLEASE PROVIDE LOADS ON |
| | EXISTING SERVICE GUTTER WITH NEW LOADS |
| | BEING ADDED. PLEASE ALSO INDICATE THE |
| | SIZE OF THE EXISTING SERVICE. |
| | 230.2, 220, 215.5 ETC |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM GUTTER TO |
| | METER, METER TO MAIN, MAIN TO SUB PANEL, |
| | PANELS TO TRANSFORMERS, AND TRANSFORMER |
| | TO PANELS. |
| | ** PLEASE KNOW, IF MAIN SERVICE FOR |
| | BUILDING CONTAINS AS MAIN , THEN PROVIDE |
| | NOTE ON PLANSFOR "FLOATING NEUTRAL" |
| | KIT REQUIRED IN METER. |
| | 250.6,250.24B, 250.110,250.6,250.122 |
| | ETC. |
| | |
| | 5) NOTE: PLEASE SHOW AND INDICATE THE |
| | GROUNDING ATTACHMENT LOCATIONS FOR NEW |
| | AND EXISTING TRANSFORMERS. |
| | PLEASE SEE 250.30,250.20,250.66, 250.58, |
| | 250.50 |
| | |
| | 6) NOTE: PLEASE SHOW LOCATIONS OF |
| | TRANSFORMERS ON PLANS. PLEASE SEE THAT A |
| | REVIEW FOR SOME CODE ITEMS CAN NOT BE |
| | DONE AT THIS TIME AS THESE ARE NOT |
| | SHOWN. |
| | PLEASE SEE INSTALLATION OF THE 112.5KVA TRANSFORMER |
| | SHALL NOT BE ABOVE CEILING |
| | AND MUST MEET ALL THE REQUIREMENTS AS |
| | NEC ARTICLES BELOW REQUIRE. |
| | PLEASE SEE 450.13B, 450.21, 450.9 ETC. |
| | ** IF TRANSFORMER(S) ARE GOING TO BE |
| | MOUNTED FROM CEILING OR WALL, PLEASE |
| | PROVIDE STRUCTURAL ENGINEERING DETAILS |
| | FOR THIS. |
| | |
| | 7) NOTE: PLEASE SEE 240.21 FOR TAPPED |
| | CONDUCTORS ON THE SECONDARY SIDE OF |
| | TRANSFORMERS CAN NOT BE VERIFIED AT THIS |
| | TIME. |
| | |
| | 8) NOTE: PLEASE SEE PANEL LPH AND LP/LP |
| | SHOULD BE SHOWN AS 400A RATED AND |
| | CONTAINING A 300A BRKR IF THIS IS GOING |
| | TO BE THE DESIGN. PLEASE SEE PANEL NOW |
| | SHOWS A 400A BRKR WITH A 300A TRIP? |
| | IF THIS TYPE OF BRKR IS GOING TOBE |
| | INSTALLED, PLEASE SUBMIT MANUFACTURES |
| | CUT/SPEC SHEETS ON THIS BREAKER, MUST |
| | INDICATE A LISTING FROM A NRTL. |
| | 110.3,90.7. |
| | |
| | 9) NOTE: PLEASE CORRELATE ALL PLANS FOR |
| | LOCATIONS OF ALL SERVICE EQUIPMENT |
| | PANELS. PLEASE SEE PANELS ON LIGHTING |
| | SHEETS ARE NOT IN THE SAME LOCATIONS AS |
| | PANELS ON POWER SHEETS. |
| | 106.1.2.FBC |
| | 110.26,240.24 ETC. |
| | |
| | 10) NOTE: PLEASE CORRELATE RISER AND |
| | PANELS FOR FEEDER SIZES. |
| | 310.16 , 240.4 |
| | PLEASE SEE NEW TRANSFORMER SHOWS 2/0'S |
| | ON PANEL AND RISER SHOWS 1/0'S. PLEASE |
| | SEE 310.16 AS THE 1/0'S AS SHOWN ARE |
| | NOTE RATED FOR OCP BEING PROVIDED. |
| | |
| | 11) NOTE: PLEASE SEE 240.6 FOR SIZING OF |
| | STANDARDOCP DEVICES. PLEASE SEE 170A |
| | BRKR BEING SHOWN FOR THE NEW TRANSFORMER |
| | WHICH DOES NOT CORRELATE TO ANY OF THE |
| | STANDARDS. |
| | 240.4, 310.16, 240.6, 450.3 |
| | |
| | 12) NOTE: PLEASE CORRELATE RISER AND |
| | PANEL SCHEDULES FOR LABELING OF PANELS. |
| | ( TWO LP1'S) |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE INDICATE THE NEW OR |
| | EXISTING SIGN CIRCUIT(S). AS REQUIRED |
| | PER 600.5 PLEASE SEE THAT EACH |
| | COMMERCIAL BUILDING AND EACH COMMERCIAL |
| | OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE |
| | OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| | OR OUTLINE LIGHTING SYSTEM USE. THE |
| | OUTLET(S) SHALL BE SUPPLIED BY A BRANCH |
| | CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. |
| | |
| | 14) NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EMERGENCY AND EXIT LTS. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 15) NOTE: PLEASE SEE PANEL SCHEDULES ARE |
| | NOT COMPLETE WITH LOAD CALCULATIONS AT |
| | THIS TIME. PLEASE PROVIDE COMPLETE LOAD CALCULATIONS ON |
| | HOW LOADS WERE DERIVED. |
| | PLEASE SEE 220.3,220.10,220.11,220.13 |
| | ETC |
| | PLEASE ALSO INDICATE AND SHOW ALL |
| | CONTINUOUS LOADS (3OR MORE HRS) AT 125%. |
| | (THERMOSTATICALLY CONTROLLED |
| | UNITS/APPLIANCES ARE IN EXCEPTION) |
| | |
| | 16) NOTE: PLEASE SEE TRANSFORMER ARE |
| | BEING SHOWN WITH WHAT APPEARS TO BE |
| | "NEUTRALS" IN THE FEEDER CONDUITS GOING |
| | TO THE TRANSFORMERS? PLEASE KNOW, AS THE TRANSFORMERS |
| | ARE CONSIDERED SEPARATELY |
| | DERIVED SYSTEMS/SERVICES, A NEUTRAL |
| | CONDUCTOR IS NOT INSTALLED. |
| | PLEASE KEEP IN MIND THE PREVIOUS COMMENT |
| | ABOVE WHICH PREVIOUSLY MENTIONED MISSING |
| | EQUIPMENT GROUNDING CONDUCTORS. |
| | |
| | 17) NOTE: PLEASE SEE2002 NEC, 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | 18) NOTE: PLEASE VERIFY NEW OR EXISTING SHOW/STOREFRONT |
| | WINDOW RECEPTS REQUIRED |
| | ABOVE WINDOWS.210.62 |
| | THESE WILL BE REQUIRED IF NOT EXISTING. |
| | PLEASE ALSO SEE 220.12 FOR LOADS TO BE |
| | ADJUSTED. |
| | |
| | 19) NOTE: PLEASE SEE COLOR CODING FOR |
| | 120/240V SYSTEM WIRING IS BEING SHOWN ON |
| | E-0, HOWEVER PLEASE SEE SYSTEM VOLTAGES |
| | ON PLANS ARE 120/208 AND 277/480V. |
| | PLEASE SEE COLOR CODING SHALL BE AS |
| | FOLLOWS. |
| | 120/208, |
| | BLACK ,RED, BLUE |
| | & |
| | 277/480V |
| | BROWN, PURPLE , YELLOW. |
| | PLEASE KNOW, "ORANGE" IS ONLY IDENTIFIED |
| | IN THE NEC FOR THE HIGH-LEG OF A OPEN |
| | DELTA SYSTEM, 120/240V. |
| | PLEASE ADJUST, 90.4 |
| | ** ALL EXISTING SYSTEMS AT THIS LOCATION |
| | AT CITY PLACE AND THIS JURISDICATION ARE |
| | COLOR CODED THIS WAY. |
| | |
| | 20) NOTE: PLEASE SEE MISSING SHUNT TRIP IDENTIFICATIONS |
| | FOR ALL ELECTRICAL |
| | FEEDING OR UNDER HOOD. LTS ETC). |
| | PLEASE SEE NFPA 2004/1998 BOTH ARE THE |
| | SAME FOR REQUIRED AUTOMATIC SHUNT UPON |
| | ACTIVATION OF ANY SURPRESSION SYSTEM. |
| | |
| | 21) NOTE: PLEASE SEE THIS IS A NEW |
| | OCCUPANCY FOR SPACE. PLEASE SEE 2004 FBC |
| | CHAPTER 13 FOR COMPLIANCE WITH THE NEW |
| | FLORIDA ENERGY CODE. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, AND 13-415.1.ABC.1.3 |
| | PLEASE PROVIDE A COMPLETE LIGHTING |
| | CONTROL SYSTEM AS REQUIRED INCLUDING |
| | CONTROLS AND DEVICES FOR ALL SEPARATE |
| | SPACES CONTAIN FLR TO CEILING HEIGHT |
| | PARTITIONS. |
| | PLEASE PROVIDE THE SCHEDULING, PLEASE |
| | PROVIDE TYPE OF OVER RIDE DEVICES, ALONG |
| | WITH THE NAX TIME OVE OVER RIDE AS |
| | DETERMINED BY THE DEVICE. ( TIMER TYPE |
| | 4HRS MAX, MOTION/OCCUPANT SENSOR TYPE |
| | 30MINS MAX). |
| | PLEASE SEE CONTROLS FOR OVER-RIDING |
| | SYSTEM SHALL ALSO BE LOCATED AT THE |
| | POINTS OF ENTRANCE INTO SPACE. PLEASE |
| | SEE THAT ANY OVER-RIDES MUST ALSO BE |
| | LOCATED SO THE OCCUPANT CAN VISUALLY SEE |
| | THE LIGTHING BEING CONTROLLED. |
| | PLEASE SUBMIT LIGHTING POWER DENSITES AS |
| | REQUIREDPER 13-415.1.AB.1, |
| | 13-415.2.ABC.1, AND TABLES 415.2.C.1, |
| | 415.2.B.1., 13-415.2.B.1 ETC ETC. |
| | PLEASE PROVIDE THE MAX ALLOWED COMPARED |
| | TO THE ACTUAL DESIGN. |
| | PLEASE SEE METHODS FOR NEW ENERGY |
| | CALCULATIONS MUST ALSO BE SUBMITTED. |
| | |
| | 22) NOTE: PLEASE INDICATE IF "LP" |
| | CONTAINS FEED-THRU LUGS OR IS THERE OCP |
| | IN LP FEEDING 2ND SECTION OF LP. |
| | |
| | 23) NOTE: PLEASE SEE 220.12,AN |
| | ADDITIONAL LOAD OF 150 VOLT-AMPERES |
| | SHALL BE INCLUDED FOR EVERY 600 MM (2 |
| | FT) OF LIGHTING TRACK OR FRACTION |
| | THEREOF. |
| | |
| | ** PLEASE KNOW, AS THERE ARE ITEMS NOT |
| | YET SUBMITTED FOR REVIEW, THERE MAY BE |
| | NEW COMMENTS UPON NEXT REVIEW. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |