| Plan Review Notes For Permit 06081935 |
| Permit Number |
06081935 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-12 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SUBMIT A PANEL SCHEDULE PER 408.4 NEC | | | AND 106.3.5.4(8) FBC. | | | | | | 2} PROVIDE A LOAD CALCULATION PER | | | 220.31, INCLUDE ADDED LOADS. | | | | | | 3} PROVIDE A RISER DIAGRAM IF CHANGING | | | THE SERVICE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|