| 2006-09-18 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT |
| | ON THE PLAN, METER ENCLOSURE, |
| | DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN |
| | BE REVIEWED. |
| | |
| | 2} A DISCONNECTING MEANS PER 225.31, |
| | LOCATED PER 225.32, AND GROUNDED PER |
| | 250.32 IS REQUIRED AT THE SEPARATE |
| | STRUCTURE. |
| | |
| | 3} PANEL "B" SCHEDULE INDICATES A 60 AMP |
| | PANEL, THE RISER AND PLAN INDICARE PANEL |
| | "B" IS 100 AMPS. PLEASE CORRELATE. |
| | |
| | 4} PLEASE VERIFY THE FEEDER AND |
| | GROUND(S) SIZE AND NUMBER TO THE |
| | "CABANA" PANEL. CORRECT ON PLAN. |
| | |
| | 5} A LIGHTING OUTLET IS REQUIRED FOR |
| | EGRESS PER 210.70(A)(2)(B). NOTE THE ONE |
| | AROUND THE CORNER FROM THE DOOR WILL NOT |
| | MEET THE INTENT. |
| | |
| | 6} THE 60 AMP OCP FOR THE WATER HEATER |
| | IS TO LARGE TO PROTECT THE 5000 WATT |
| | LOAD. SEE 422.13 AND 240.6. |
| | |
| | 7} PLEASE SEE NOTE #7 REGARDING JUNCTION |
| | BOXES AND REFERENCING 370.17 ARE FROM |
| | THE 1996 CODE. THE CODE CURRENTLY |
| | ADOPTED IS 2002 NEC. PLEASE CORRECT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |