| Date |
Text |
| 2006-10-03 00:00:00 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, |
| | AND A COPY OF THE PAID RECEIPT ATTACHED |
| | TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 3.BASED ON ICC BUILDING VALUATION DATA |
| | THE PERMIT VALUE HAS BEEN REVISED TO |
| | $31,224.ADDITIONAL PERMIT FEES ARE |
| | DUE. |
| | |
| | 4.SUBMIT TWO ORIGINAL SIGNED AND |
| | SEALED SURVEYS. FS 472.025 |
| | |
| | 5.PRODUCT APPROVALS REQUIRED FOR |
| | LINTELS. |
| | |
| | 6.ALL PRODUCT APPROVALS SUBMITTED WITH |
| | QUALITY ASSURANCE SHALL HAVE THE |
| | FOLLOWING STATE APPROVAL ATTACHED. |
| | NOTE:ALL STATE APPROVALS SUBMITTED ARE |
| | THE WRONG PAGES EXCEPT THE OVER HEAD |
| | DOOR PRODUCT APPROVAL. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL |
| | SHEETS THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT |
| | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| | AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.FLAT ROOF PRODUCT APPROVAL.SELECT |
| | ASSEMBLY USED AND CHECK GENERAL |
| | LIMITATION NUMBER 7.CALCULATIONS MAY |
| | BE REQUIRED. |
| | |
| | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS |
| | FOR REVIEW PER 2004 FBC R-802.10.1 |
| | TRUSS DRAWING REQUIRED TO BE APPROVED |
| | PRIOR TO INSTALLATION. |
| | |
| | 9.R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| | STORM SEWER CONVEYANCE OR OTHER APPROVED |
| | POINT OF COLLECTION SO AS TO NOT CREATE |
| | A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| | WALLS. THE GRADE AWAY FROM FOUNDATION |
| | WALLS SHALL FALL A MINIMUM OF 6 INCHES |
| | WITHIN THE FIRST 10 FEET. |
| | |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | OLD PAGES FOR REFERENCE . A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ART LANGE |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | BUILDING PLANS EXAMINER |
| | 561-805-6672 |
| | |
| | |
| | |
| | |