| | REVISION DENIED |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE CLOUD OR OTHERWISE NOTE REVISION FOR CLARITY |
| | AND RECORD RETENTION. 106.1.3, AS AMENDED. |
| | |
| | 2} NOTE #8 SHEET E1 INDICATES THE USE OF "NMPT". NOTE |
| | THE SCOPE PER UL WOULD PROHIBIT USE OF THAT TUBING: |
| | NONMETALLIC MECHANICAL PROTECTION TUBING (NMPT) |
| | UL 1696 |
| | |
| | 1 SCOPE |
| | 1.1 THIS STANDARD APPLIES TO NONMETALLIC MECHANICAL |
| | PROTECTION TUBING (NMPT) AND FITTINGS IN 10 TO 53 (1/4 |
| | TO 2) TRADE SIZES FOR USE AS SUPPORT AND PROTECTION OF |
| | INSULATED CONDUCTORS IN EQUIPMENT INTENDED FOR USE IN |
| | NON-HAZARDOUS LOCATIONS. FOR TUBING AND FITTING SIZES |
| | IN THIS STANDARD, THE METRIC DESIGNATOR IS GIVEN FIRST, |
| | WITH THE TRADE SIZE IN INCHES FOLLOWING IN |
| | PARENTHESES. |
| | |
| | |
| | 1.2 TUBING SPECIFIED BY THIS STANDARD IS INTENDED FOR |
| | USE WITH FITTINGS IN COMPLIANCE WITH CLAUSE 4.3. THE |
| | FITTINGS MAY BE FOR WET OR DRY LOCATIONS. |
| | |
| | 1.3 THIS STANDARD DOES NOT INCLUDE TUBING USED TO |
| | SUPPLY POWER FROM THE FIXED WIRING OF STRUCTURES TO |
| | UTILIZATION EQUIPMENT. |
| | |
| | 3} SHEETS E5 AND E6 ARE NOT REVISIONS OF THOSE SAME |
| | NUMBERED SHEETS ON THE PERMITTED SET. CORRELATE REVISED |
| | SHEET NUMBERS TO THE SHEET BEING REVISED FOR RECORD |
| | KEEPING AND CLARITY IN THE FIELD. 106.1.3 FBC AS |
| | AMENDED. |
| | |
| | NOTE: SEE FIRE PLAN REVIEW FOR COMMENTS ON ADDRESS. |
| | |