Plan Review Notes
Plan Review Notes For Permit 06081925
Permit Number 06081925
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-25 10:28:36 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE CLOUD OR OTHERWISE NOTE REVISION FOR CLARITY
 AND RECORD RETENTION. 106.1.3, AS AMENDED.
  
 2} NOTE #8 SHEET E1 INDICATES THE USE OF "NMPT". NOTE
 THE SCOPE PER UL WOULD PROHIBIT USE OF THAT TUBING:
 NONMETALLIC MECHANICAL PROTECTION TUBING (NMPT)
 UL 1696
  
 1 SCOPE
 1.1 THIS STANDARD APPLIES TO NONMETALLIC MECHANICAL
 PROTECTION TUBING (NMPT) AND FITTINGS IN 10 TO 53 (1/4
 TO 2) TRADE SIZES FOR USE AS SUPPORT AND PROTECTION OF
 INSULATED CONDUCTORS IN EQUIPMENT INTENDED FOR USE IN
 NON-HAZARDOUS LOCATIONS. FOR TUBING AND FITTING SIZES
 IN THIS STANDARD, THE METRIC DESIGNATOR IS GIVEN FIRST,
 WITH THE TRADE SIZE IN INCHES FOLLOWING IN
 PARENTHESES.
  
  
 1.2 TUBING SPECIFIED BY THIS STANDARD IS INTENDED FOR
 USE WITH FITTINGS IN COMPLIANCE WITH CLAUSE 4.3. THE
 FITTINGS MAY BE FOR WET OR DRY LOCATIONS.
  
 1.3 THIS STANDARD DOES NOT INCLUDE TUBING USED TO
 SUPPLY POWER FROM THE FIXED WIRING OF STRUCTURES TO
 UTILIZATION EQUIPMENT.
  
 3} SHEETS E5 AND E6 ARE NOT REVISIONS OF THOSE SAME
 NUMBERED SHEETS ON THE PERMITTED SET. CORRELATE REVISED
 SHEET NUMBERS TO THE SHEET BEING REVISED FOR RECORD
 KEEPING AND CLARITY IN THE FIELD. 106.1.3 FBC AS
 AMENDED.
  
 NOTE: SEE FIRE PLAN REVIEW FOR COMMENTS ON ADDRESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]