| 2006-10-13 16:02:59 | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ENGINEER OF RECORD SHALL INDICATE THE |
| | CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER |
| | INFORMATION REQUIRED BY 61G15-23.002FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2} PROVIDE A DETAIL INDICATING COMPLIANCE WITH ARTICLE |
| | 501 NECAND 30A NFPA FOR THE ELECTRICAL CONNECTIIONS |
| | AT THE FUEL DISPENSING SYSTEM ON THE DOCKS. |
| | |
| | 3} PLEASE SUBMIT DETAILS OF THE "DATACOM" PEDESTALS |
| | LIKE THE ONES SUBMITTED FOR THE POWER PEDESTALS. |
| | INDICATE IF THE CONDUIT SYSTEM IS INDEPENDENT OF THE |
| | BELLINGHAM SYSTEM OR PART OF SAME SYSTEM. THERE DOESN'T |
| | APPEAR TO BE HANDHOLES OR PULLING POINTS. PLEASE |
| | CLARIFY. |
| | |
| | 4} THERE WERE DRAWINGS SUBMITTED FROM MEISNER ELECTRIC, |
| | WHICH MUST CONTAIN THE PRINTED NAME AND WRITTEN |
| | SIGNATURE OF THE DESIGNER PER 106.3.4.2 FBC AS AMENDED, |
| | OR CHAPTER 471 FS IF APPLICABLE. THERE WERE ALSO |
| | DRAWINGS ON SHEET E5 OF THE ELECTRICAL PLANS FOR THIS |
| | SYSTEM. PLEASE INDICATE WHICH ONE WILL BE SUBMITTED FOR |
| | PERMITTING, WHICH DESIGNER IS TAKING RESPONSIBILITY. |
| | |
| | 5} SUBMIT DETAILS FOR THE MOUNTING AND WIRING FOR THE |
| | CCTV CAMERAS SHOWN ON THE PLANS. |
| | |
| | 6} SUBMIT A COMPLETE RACEWAY SYSTEM FOR THE POWER POINT |
| | PEDESTAL FEEDERS. SUBMITTED WERE CONDUITS , CABLES AND |
| | THWN, ALL OF WHICH WILL BE EXPOSED AND NOT PART OF ANY |
| | SYSTEM BETWEEN DOCK SECTIONS. SEE NEC.300.4 PROTECTION |
| | AGAINST PHYSICAL DAMAGE. |
| | WHERE SUBJECT TO PHYSICAL DAMAGE, CONDUCTORS SHALL BE |
| | ADEQUATELY PROTECTED. |
| | |
| | 7} THE SPECIFICATION SECTION ON E2 INCORRECTLY |
| | REFERENCES THE 2005 EDITION OF THE NEC, THE CODE |
| | CURRENTLY ADOPTED BY THE FLORIDA LEGISLATURE IS 2002. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |