| Plan Review Notes For Permit 06081920 |
| Permit Number |
06081920 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-09-11 18:08:15 | *** PROVISO*** | | | | | | 1) NOTE: PLEASE INSTALL AN ADDITIONAL BATTERY BACK | | | LIGHT OF SOME KIND IN NEW LARGE CLASSROOM PER NFPA-101 | | | 7.8, 7.9 | | | ** CIRCUIT PER 700.12E OF THE 2002 NEC/700.12F OF THE | | | 2005 NEC TO A LOCAL BRANCH LIGHTING CIRCUIT. | | | ** OTHER EXIT AND EMERGENCY LIGHTING FIXTURES TO VERIFY | | | CIRCUITING. | | | | | | 2) NOTE: PLEASE SUBMIT DETAILS AND TYPE OF SPECIFIC | | | OCCUPANCY DEVICES PER 13-415.1.ABC.1.1. THIS WAS ONLY | | | STATED IN A NOTE ON PLANS. NEED DETAIL. | | | PLEASE DETERMINE AND INDICATE THE MAXIMUM LIGHTING | | | POWER DENSITIES PER 13-415.2, TABLE 13-415.2.C.1, AND | | | 13-415.2.B.1. | | | FBC 106.1, 106.1.2 | | | | | | 3) NOTE: PLEASE REVISE CIRCUITING AND LOAD CALCULATIONS | | | TO MEET THE MINIMUM PER NEC 220 AND 408.4. | | | VERIFY CIRCUITING TO RECEPTACLES AND LIGHTING AS | | | SHOWN. | | | PLEASE SEE LOAD FOR LIGHTING IS UNCLEAR. | | | | | | *** PLEASE CALL TO GO OVER ANY OF THESE COMMENTS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|