Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop E
Sequence Number 5
Notes
Date Text
2007-09-11 18:08:15*** PROVISO***
  
 1) NOTE: PLEASE INSTALL AN ADDITIONAL BATTERY BACK
 LIGHT OF SOME KIND IN NEW LARGE CLASSROOM PER NFPA-101
 7.8, 7.9
 ** CIRCUIT PER 700.12E OF THE 2002 NEC/700.12F OF THE
 2005 NEC TO A LOCAL BRANCH LIGHTING CIRCUIT.
 ** OTHER EXIT AND EMERGENCY LIGHTING FIXTURES TO VERIFY
 CIRCUITING.
  
 2) NOTE: PLEASE SUBMIT DETAILS AND TYPE OF SPECIFIC
 OCCUPANCY DEVICES PER 13-415.1.ABC.1.1. THIS WAS ONLY
 STATED IN A NOTE ON PLANS. NEED DETAIL.
 PLEASE DETERMINE AND INDICATE THE MAXIMUM LIGHTING
 POWER DENSITIES PER 13-415.2, TABLE 13-415.2.C.1, AND
 13-415.2.B.1.
 FBC 106.1, 106.1.2
  
 3) NOTE: PLEASE REVISE CIRCUITING AND LOAD CALCULATIONS
 TO MEET THE MINIMUM PER NEC 220 AND 408.4.
 VERIFY CIRCUITING TO RECEPTACLES AND LIGHTING AS
 SHOWN.
 PLEASE SEE LOAD FOR LIGHTING IS UNCLEAR.
  
 *** PLEASE CALL TO GO OVER ANY OF THESE COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]