| 2007-07-27 12:15:41 | | | | *** UNSATREVIEW *** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL | | | REMAIN AND PLEASE SEE THERE ARE NEW COMMENTS BASED ON | | | CHANGES MADE TO THE PLANS. | | | | | | | | | 1) NOTE: PLEASE SEE THE SCOPE OF WORK SEEMS TO HAVE | | | BEEN REDUCED HOWEVER THE CIRCUITING NOW SHOWN ON PLANS | | | DOES NOT CORRELATE WITH EITHER OF THE PANEL SCHEDULES | | | PROVIDED. | | | PLEASE SEE THERE ARE 120V RECEPTACLE CIRCUITS SHOWN TO | | | AIR CONDITIONING 220V LOADS. PLEASE SEE OTHER ROOMS AND | | | AREAS WHICH DO NOT CORRELATE. | | | PLEASE SEE PANEL SCHEDULE NOW SHOWS 20AMP SUB PANEL | | | FEED. | | | PLEASE VERIFY RISER AND ALL PANELS. | | | FBC 106.3.5.1.2 | | | NEC 408.4, 310.16, 240.4 ETC. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW A *PROVISO* WAS | | | GIVEN TO HAVE CORRECTIONS MADE TO PLANS IF THEY ARE | | | REJECTED BY ANY OTHER TRADES FOR LIGHTING CONTROLS AS | | | REQUIRED PER 13-415.1.ABC.1.1 AND .1.2. | | | PLEASE SEE THE NEW LIGHTING CONTROLS NEED TO BE SHOWN. | | | 13-101 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|