Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop P
Sequence Number 3
Notes
Date Text
2007-04-09 16:43:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.3.
 ****COMMENT NOT ADDRESSED FOR THE NEW STAFF BATHROOM.
 THIS SHALL BE SHOWN ON ALL SHEETS, NOT JUST THE
 ARCHITECTURAL.
  
 3. SUBMIT A DETAIL FOR THE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 __FOR THE W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE. THIS SHALL BE SHOWN
 FOR THE W/C'S ON THE FLOOR PLAN OF EACH ROOM.
 B. 11-4.16.4 GRAB BARS. THE SECTION THRU BATHROOM
 INDICATES THE SIDE GRAB BAR AS 2'0". THE REQUIRED
 LENGTH IS 42" SEE FIG 29.
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 __FOR THE URINAL:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 __FOR THE LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE. SHOW IN EACH TOILET
 ROOM AND THE NEW BATHROOM.
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 __FOR THE SHOWER:
 A. 11-4.21.2 SIZE AND CLEARANCE
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 NOTE: ELEVATIONS FOR THE FIXTURES MAY BE REQUIRED TO
 INDICATE ALL CODE REQUIREMENTS. W/C'S SHALL BE SHOWN
 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE, AND
 THE LAVS SHALL BE SHOWN 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURES FOR EACH TOILET ROOM. SEE
 FIGS. 28, 35B & 37B.
  
 4. SUBMIT A DETAIL FOR THE NEW BATHROOM.
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS.
 ****NOT COMPLETLY ADDRESSED. SEE COMMENT #3.-THE
 TOILET SHALL BE SHOWN 18" OFF THE SHOWER OR LAV AND 15"
 OFF THE OTHER FIXTURE WITH A MINIMUM 33" OPENING
 BETWEEN THE LAV AND SHOWER.
  
 5. OK
 6. OK
  
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, TRAPS, VENTS ETC.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE URINAL
 WASTE LINE CONNECTING TO THE BRANCH LINE PRIOR TO THE
 W/C'S AND LAVS, BUT THE RISER SHOWS THE URINAL
 CONNECTING UPSTREAM OF THE LAST W/C. (SEE EXAMPLE ON
 ONE P-1 SHEET).
  
 8. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, VALVES, WATER
 HAMMER ARRESTORS (IF REQUIRED BY SECTION
 604.9). SECTION 106.1.1 AND SECTION 606. ****RESPONSE
 NOTED, BUT THE PIPE SIZING IS NOT SUFFICIENT. ALL STUB
 OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT THE URINAL 3/4".
 THE URINAL IS NOT EVEN SHOWN ON THE WATER RISER
 DIAGRAM. SEE TABLES 603.1 & 709.1. SERVICE TO THE UNIT
 SHOULD BE 1" AND A SHUT OFF VALVE IS ALSO REQUIRED ON
 THE SERVICE TO THE UNIT. PLEASE INDICATE ON PLANS.
  
 ********NEW COMMENT********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A
 NOTICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]