| 2007-04-09 16:43:32 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | |
| | 2. DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | SECTION 11-4.22.3. |
| | ****COMMENT NOT ADDRESSED FOR THE NEW STAFF BATHROOM. |
| | THIS SHALL BE SHOWN ON ALL SHEETS, NOT JUST THE |
| | ARCHITECTURAL. |
| | |
| | 3. SUBMIT A DETAIL FOR THE TOILET ROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | __FOR THE W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE. THIS SHALL BE SHOWN |
| | FOR THE W/C'S ON THE FLOOR PLAN OF EACH ROOM. |
| | B. 11-4.16.4 GRAB BARS. THE SECTION THRU BATHROOM |
| | INDICATES THE SIDE GRAB BAR AS 2'0". THE REQUIRED |
| | LENGTH IS 42" SEE FIG 29. |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | D. 11-4.16.6 DISPENSERS |
| | __FOR THE URINAL: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | __FOR THE LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE. SHOW IN EACH TOILET |
| | ROOM AND THE NEW BATHROOM. |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | __FOR THE SHOWER: |
| | A. 11-4.21.2 SIZE AND CLEARANCE |
| | B. 11-4.21.3 SEAT |
| | C. 11-4.21.4 GRAB BARS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.6 SHOWER UNIT |
| | F. 11-4.21.7 CURBS |
| | NOTE: ELEVATIONS FOR THE FIXTURES MAY BE REQUIRED TO |
| | INDICATE ALL CODE REQUIREMENTS. W/C'S SHALL BE SHOWN |
| | 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE, AND |
| | THE LAVS SHALL BE SHOWN 15" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURES FOR EACH TOILET ROOM. SEE |
| | FIGS. 28, 35B & 37B. |
| | |
| | 4. SUBMIT A DETAIL FOR THE NEW BATHROOM. |
| | SHOW COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS. |
| | ****NOT COMPLETLY ADDRESSED. SEE COMMENT #3.-THE |
| | TOILET SHALL BE SHOWN 18" OFF THE SHOWER OR LAV AND 15" |
| | OFF THE OTHER FIXTURE WITH A MINIMUM 33" OPENING |
| | BETWEEN THE LAV AND SHOWER. |
| | |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SUBMIT A SANITARY RISER ISOMETRIC |
| | DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, TRAPS, VENTS ETC. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE URINAL |
| | WASTE LINE CONNECTING TO THE BRANCH LINE PRIOR TO THE |
| | W/C'S AND LAVS, BUT THE RISER SHOWS THE URINAL |
| | CONNECTING UPSTREAM OF THE LAST W/C. (SEE EXAMPLE ON |
| | ONE P-1 SHEET). |
| | |
| | 8. SUBMIT A WATER RISER ISOMETRIC |
| | DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, VALVES, WATER |
| | HAMMER ARRESTORS (IF REQUIRED BY SECTION |
| | 604.9). SECTION 106.1.1 AND SECTION 606. ****RESPONSE |
| | NOTED, BUT THE PIPE SIZING IS NOT SUFFICIENT. ALL STUB |
| | OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT THE URINAL 3/4". |
| | THE URINAL IS NOT EVEN SHOWN ON THE WATER RISER |
| | DIAGRAM. SEE TABLES 603.1 & 709.1. SERVICE TO THE UNIT |
| | SHOULD BE 1" AND A SHUT OFF VALVE IS ALSO REQUIRED ON |
| | THE SERVICE TO THE UNIT. PLEASE INDICATE ON PLANS. |
| | |
| | ********NEW COMMENT******** |
| | |
| | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |