| Plan Review Notes For Permit 06081920 |
| Permit Number |
06081920 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-24 15:12:10 | ** PROVISO ** | | | | | | 1) NOTE: PLEASE SEE NEW CLASSROOMS WITH NEW LIGHTING | | | AND NEW LIGHTING CONTROLS SHALL MEET FBC 2004 CHAPTER | | | 13. | | | PLEASE SEE 13-415.1.ABC.1.1, AND .1.2 AS AUTOMATED | | | CONTROLS FOR NEW LIGHTING IN THESE ROOMS IS REQUIRED. | | | THIS CAN BE ACCOMPLISHED BY THE USE OF WALL CONTROL | | | OCCUPANCY SENSORS WHICH WILL STAY ON FOR NO MORE THAN | | | 30MINS AFTER THE LAST SENSING OF THE OCCUPANT. THIS WAS | | | CONFIRMED WITH THE FLORIDA BUILDING COMMISSION SINCE | | | THE LAST REVIEW THAT NEW INSTALLATIONS REGARDLESS OF | | | THE TOTAL AMOUNT OF SPACE BEING RENOVATED STILL | | | REQUIRES CONTROLS FOR NEW. THIS WOULD INCLUDE THE FIVE | | | NEW CLASSROOMS, NEW MEN?S, WOMEN?S AND STAFF | | | BATHROOMS. | | | **PLEASE SUBMIT REVISED PLANS BEFORE ROUGH ELECTRICAL | | | INSPECTION FOR REVIEW, STAMPING AND TO BE BACK ON THE | | | SITE FOR INSPECTOR. | | | | | | | | | ** IF PLANS ARE RETURNED FOR ANY CORRECTIONS FROM OTHER | | | TRADES, PLEASE CORRECT. | | | | | | ** IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE | | | IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|