2007-03-24 15:12:10** PROVISO **
  
 1) NOTE: PLEASE SEE NEW CLASSROOMS WITH NEW LIGHTING
 AND NEW LIGHTING CONTROLS SHALL MEET FBC 2004 CHAPTER
 13.
 PLEASE SEE 13-415.1.ABC.1.1, AND .1.2 AS AUTOMATED
 CONTROLS FOR NEW LIGHTING IN THESE ROOMS IS REQUIRED.
 THIS CAN BE ACCOMPLISHED BY THE USE OF WALL CONTROL
 OCCUPANCY SENSORS WHICH WILL STAY ON FOR NO MORE THAN
 30MINS AFTER THE LAST SENSING OF THE OCCUPANT. THIS WAS
 CONFIRMED WITH THE FLORIDA BUILDING COMMISSION SINCE
 THE LAST REVIEW THAT NEW INSTALLATIONS REGARDLESS OF
 THE TOTAL AMOUNT OF SPACE BEING RENOVATED STILL
 REQUIRES CONTROLS FOR NEW. THIS WOULD INCLUDE THE FIVE
 NEW CLASSROOMS, NEW MEN?S, WOMEN?S AND STAFF
 BATHROOMS.
 **PLEASE SUBMIT REVISED PLANS BEFORE ROUGH ELECTRICAL
 INSPECTION FOR REVIEW, STAMPING AND TO BE BACK ON THE
 SITE FOR INSPECTOR.
  
  
 ** IF PLANS ARE RETURNED FOR ANY CORRECTIONS FROM OTHER
 TRADES, PLEASE CORRECT.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE
 IN CONTACTING THIS OFFICE.
  