| 2007-03-30 17:32:05 | BUILDING PLAN REVIEW |
| | PERMIT: 06081920 |
| | ADD: 1750 N. FLORIDA MANGO RD. #302 |
| | CONT: BILL MARTIN RENAVATIONS INC. |
| | TEL: (561)863-8227 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 3RD |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)THE INFORMATION SUBMITTED FOR THE HEAD + FLOOR |
| | DETAIL SHALL INDICATEHOW OR WHAT THE BLOCKING WILL BE |
| | ATTATCHED TO AND THE MATERIALS USED TO SECURE IT. WILL |
| | THE BLOCKING BE ATTATCHED TO THE CEILING OR THE |
| | STRUCTURE ABOVE? AND WHAT IS THE ROOF STRUCTURE?. SEE |
| | NOTE #2 FROM PREVIOUS REVIEW. |
| | |
| | 3)THE INFORMATION FOR THE PARTITION WAS NOT |
| | RESUBMITTED. THE POCKET DOORS SHOWN ON THE DETAIL FOR |
| | THE MOVEABLE PARTIONS ARE NOT INDICATED ON THE |
| | DRAWINGS. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROSED AND SHOW IN DETAIL THAT IT WILL CONFORM |
| | TO THE CODE.PLEASE SEE NOTES FROM LAST REVIEW WERE |
| | NOT ADDRESSED. |
| | |
| | 4) SHOW THE CLEAR FLOOR SPACE FOR THE TOILET AND |
| | BATHROOMS COMPLYING WITH SECTIONS 11-4.16,11-4.19, |
| | FIG. 28 AND 30E. |
| | |
| | 5)NOTE FROM FIRST REVIEW (2)FBC. 11-4.22.2 ALL |
| | DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH SEC. |
| | 11-4.13 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE. SEE NEW STAFF |
| | BATH/MEN'S AND WOMEN'S TOILETS. |
| | |
| | 6)SHEET A-1. THE OCCUPANT LOAD INDICATED IS |
| | INCORRECT. CLARIFY.AND SEE FBC. 1004. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |