Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop P
Sequence Number 2
Notes
Date Text
2006-12-09 07:25:18DENIED;
 SEE SOME NOTES FROM 1ST REVIEW WERE NOT ADDREESED;
 1. OK
 2. NO; DID NOT CHANGE DOOR SWING ON PAGE P-1.
 3. NO; DETAIL NOT SHOWN FOR HANDICAP TOILET ROOMS, AND
 NEW STAFF BATH, THAT IS REQUIRED TO BE HANDICAPED.
 SECTION 11-4.1.3(11). ALSO SHOW A DETAIL OF URINAL,
 TURNING RADIUS AND CLEAR FLOOR SPACE ON DRAWINGS.
 4. NO; SEE NOTE 3. COMPLIANCE TO SECTIONS 11-4.16,
 11-4.18, 11-4.19 AND 11-4.22 ARE NOT SHOWN.
 5. NO; OCCUPANCY SHOULD BE EDUCATIONAL, ONE SEVICE SINK
 IS REQUIRED TABLE 403.1 SECTION 3 E/D.
 6. OK
 7. OK WITH CHANGES SEE ONE SET OF PLANS MARKED IN RED.
 8. WATER RISER SUBMITED BUT DOES NOT MEET CODE. ALL
 STUB OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT URINAL 3/4"
 REQUIRED. PIPE SIZING IS INCORRECT. SEE TABLES 603.1
 AND 709.1. SEVICE TO UNIT SHOULD BE 1". A SHUTOFF VALVE
 IS ALSO REQUIRED ON SERVICE TO UNIT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved