| Plan Review Notes For Permit 06081920 |
| Permit Number |
06081920 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-09 07:25:18 | DENIED; | | | SEE SOME NOTES FROM 1ST REVIEW WERE NOT ADDREESED; | | | 1. OK | | | 2. NO; DID NOT CHANGE DOOR SWING ON PAGE P-1. | | | 3. NO; DETAIL NOT SHOWN FOR HANDICAP TOILET ROOMS, AND | | | NEW STAFF BATH, THAT IS REQUIRED TO BE HANDICAPED. | | | SECTION 11-4.1.3(11). ALSO SHOW A DETAIL OF URINAL, | | | TURNING RADIUS AND CLEAR FLOOR SPACE ON DRAWINGS. | | | 4. NO; SEE NOTE 3. COMPLIANCE TO SECTIONS 11-4.16, | | | 11-4.18, 11-4.19 AND 11-4.22 ARE NOT SHOWN. | | | 5. NO; OCCUPANCY SHOULD BE EDUCATIONAL, ONE SEVICE SINK | | | IS REQUIRED TABLE 403.1 SECTION 3 E/D. | | | 6. OK | | | 7. OK WITH CHANGES SEE ONE SET OF PLANS MARKED IN RED. | | | 8. WATER RISER SUBMITED BUT DOES NOT MEET CODE. ALL | | | STUB OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT URINAL 3/4" | | | REQUIRED. PIPE SIZING IS INCORRECT. SEE TABLES 603.1 | | | AND 709.1. SEVICE TO UNIT SHOULD BE 1". A SHUTOFF VALVE | | | IS ALSO REQUIRED ON SERVICE TO UNIT. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|