| 2006-11-22 16:42:44 | ***** UNSAT 2ND REVIEW ******* |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND |
| | SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED |
| | OF ADDRESSING. |
| | |
| | |
| | 1) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES NOW BEING SUBMITTED. |
| | PLEASE SEE CIRCUITS ARE NOTED WITH A NUMERICAL |
| | DESIGNATION ONLY AND NOTHING TO A PANEL LETTER OR |
| | NUMBER. |
| | PLEASE SEE THERE ARE CIRCUITS ON PLANS WHICH DO NOT |
| | MATCH WITH EITHER OF THE PANEL SCHEDULES. |
| | PLEASE SEE THE INSTA-HOT WHICH IS BEING SHOWN ON |
| | CIRCUIT 18/20 ON PANEL #1, HOWEVER PLANS INDICATE |
| | CIRCUIT # 36/38? |
| | PLEASE SEE OTHER CIRCUITS WHICH ARE BEING SHOWN AS |
| | EXISTING ON PANEL SCHEDULES; HOWEVER THESE ARE IN AREAS |
| | WHICH ARE NEW. |
| | PLEASE SEE SOME OTHER ELECTRICAL DEVICES/FIXTURES ON |
| | PLANS WHICH CONTAIN NO CIRCUITING. |
| | 408.4, 310.16, ETC |
| | FBC 106.1.2 ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | PREVIOUSLY NOTED. |
| | |
| | 2) NOTE: PLEASE SEE 700.12E FOR THE CIRCUITING OF THE |
| | EXIT AND EMERGENCY LIGHTS AS REQUIRED. |
| | PLEASE SEE THAT THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 3) NOTE: PLEASE SHOW ALL MINIMUM CONDUCTOR SIZES ON |
| | PANEL SCHEDULES FOR CIRCUITS AS SHOWN BASED ON |
| | 240.4,310.16, 220.19-220.24 |
| | PLEASE SEE RESPONSE LETTER MENTIONS THIS IS DONE ON |
| | PLANS, HOWEVER NONE OF THESE WERE LOCATED ON PANEL |
| | SCHEDULES. UNABLE TO VERIFY COORDINATION OF ANY OVER |
| | CURRENT PROTECTIVE DEVICES AND CONDUCTOR SIZES AT THIS |
| | TIME. |
| | PREVIOUSLY NOTED. |
| | |
| | 4) NOTE: PLEASE INDICATE THE CURRENT CODES RELEVANT AND |
| | IN EFFECT FOR SAID PROJECT AS PREVIOUSLY REQUESTED. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101. |
| | |
| | 5) NOTE: PLEASE LOADS ON CIRCUITS SHALL BE SHOWN. |
| | PLEASE SEE RECEPTACLE CIRCUITS WHICH ARE SUBSTANTIALLY |
| | OVERLOADED. PLEASE SEE 220.13. |
| | PLEASE ALSO SEE NEW ADDED LOAD FOR TANK-LESS WATER |
| | HEATER WHICH IS NOT SHOWN IN ANY CALCULATIONS. |
| | PLEASE SUBMIT CALCULATIONS AND THE ACTUAL SIZE OF THE |
| | EXISTING SERVICE, NOT ONLY THE PANEL SIZES. |
| | PLEASE SEE 220.3,220.10,220.11,220.13,AND 215.3, |
| | 230.42 FOR CONTINUOUS LOADS. |
| | PLEASE SEE FBC ADMIN SECT. 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE PANEL #1 AND #2 ARE BEING NOTED AS |
| | GOING DIRECTLY TO THE EXISTING METER, HOWEVER IF THESE |
| | CONTAIN MAINS, THEY ARE NOT GROUPED. PLEASE VERIFY |
| | THIS. |
| | 230.2, 230.72 ETC. |
| | |
| | 7) NOTE: PLEASE ALSO SEE A 50A SUB PANEL IS BEING SHOWN |
| | ON RISER BEING FED FROM PANEL #2 , YET THIS PANEL #3 ON |
| | THE PANEL SCHEDULE #2 IS BEING FROM TWO SEPARATE SINGLE |
| | POLE 20A BREAKERS??? |
| | PLEASE VERIFY THIS. |
| | PLEASE SEE 240.4,310.16,240,ETC. |
| | THERE ARE TOO MANY CODE SECTIONS TO LIST. |
| | |
| | 8) NOTE: PLEASE SEE GENERAL NOTES #5. PLEASE SEE THIS |
| | DOES NOT SEEM TO BE ACCURATE FOR THE WORK BEING DONE ON |
| | THIS PROJECT. |
| | FBC 106.1.2,NEC 310.16. |
| | |
| | 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW ONE COPY OF ELECTRICAL PLANS ARE BEING |
| | RETAINED AND ONE SET OF RED-LINED PLANS WILL GO BACK TO |
| | CONTRACTOR ONCE ALL REVIEWS ARE DONE. |
| | |
| | 10) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS /CUT |
| | SHEETS FOR THE NEW TANK LESS WATER HEATER. PLEASE KNOW |
| | THIS MUST CONTAIN A LISTING FROM A NRTL. (NATIONALLY |
| | RECOGNIZED TESTING LABORATORY). |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN |
| | SUBMITTED, PLEASE KNOW THERE MAY BE COMMENTSON NEXT |
| | REVIEW. |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |