Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-22 16:42:44***** UNSAT 2ND REVIEW *******
  
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND
 SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED
 OF ADDRESSING.
  
  
 1) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES NOW BEING SUBMITTED.
 PLEASE SEE CIRCUITS ARE NOTED WITH A NUMERICAL
 DESIGNATION ONLY AND NOTHING TO A PANEL LETTER OR
 NUMBER.
 PLEASE SEE THERE ARE CIRCUITS ON PLANS WHICH DO NOT
 MATCH WITH EITHER OF THE PANEL SCHEDULES.
 PLEASE SEE THE INSTA-HOT WHICH IS BEING SHOWN ON
 CIRCUIT 18/20 ON PANEL #1, HOWEVER PLANS INDICATE
 CIRCUIT # 36/38?
 PLEASE SEE OTHER CIRCUITS WHICH ARE BEING SHOWN AS
 EXISTING ON PANEL SCHEDULES; HOWEVER THESE ARE IN AREAS
 WHICH ARE NEW.
 PLEASE SEE SOME OTHER ELECTRICAL DEVICES/FIXTURES ON
 PLANS WHICH CONTAIN NO CIRCUITING.
 408.4, 310.16, ETC
 FBC 106.1.2 ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
 PREVIOUSLY NOTED.
  
 2) NOTE: PLEASE SEE 700.12E FOR THE CIRCUITING OF THE
 EXIT AND EMERGENCY LIGHTS AS REQUIRED.
 PLEASE SEE THAT THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 3) NOTE: PLEASE SHOW ALL MINIMUM CONDUCTOR SIZES ON
 PANEL SCHEDULES FOR CIRCUITS AS SHOWN BASED ON
 240.4,310.16, 220.19-220.24
 PLEASE SEE RESPONSE LETTER MENTIONS THIS IS DONE ON
 PLANS, HOWEVER NONE OF THESE WERE LOCATED ON PANEL
 SCHEDULES. UNABLE TO VERIFY COORDINATION OF ANY OVER
 CURRENT PROTECTIVE DEVICES AND CONDUCTOR SIZES AT THIS
 TIME.
 PREVIOUSLY NOTED.
  
 4) NOTE: PLEASE INDICATE THE CURRENT CODES RELEVANT AND
 IN EFFECT FOR SAID PROJECT AS PREVIOUSLY REQUESTED.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
  
 5) NOTE: PLEASE LOADS ON CIRCUITS SHALL BE SHOWN.
 PLEASE SEE RECEPTACLE CIRCUITS WHICH ARE SUBSTANTIALLY
 OVERLOADED. PLEASE SEE 220.13.
 PLEASE ALSO SEE NEW ADDED LOAD FOR TANK-LESS WATER
 HEATER WHICH IS NOT SHOWN IN ANY CALCULATIONS.
 PLEASE SUBMIT CALCULATIONS AND THE ACTUAL SIZE OF THE
 EXISTING SERVICE, NOT ONLY THE PANEL SIZES.
 PLEASE SEE 220.3,220.10,220.11,220.13,AND 215.3,
 230.42 FOR CONTINUOUS LOADS.
 PLEASE SEE FBC ADMIN SECT. 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE PANEL #1 AND #2 ARE BEING NOTED AS
 GOING DIRECTLY TO THE EXISTING METER, HOWEVER IF THESE
 CONTAIN MAINS, THEY ARE NOT GROUPED. PLEASE VERIFY
 THIS.
 230.2, 230.72 ETC.
  
 7) NOTE: PLEASE ALSO SEE A 50A SUB PANEL IS BEING SHOWN
 ON RISER BEING FED FROM PANEL #2 , YET THIS PANEL #3 ON
 THE PANEL SCHEDULE #2 IS BEING FROM TWO SEPARATE SINGLE
 POLE 20A BREAKERS???
 PLEASE VERIFY THIS.
 PLEASE SEE 240.4,310.16,240,ETC.
 THERE ARE TOO MANY CODE SECTIONS TO LIST.
  
 8) NOTE: PLEASE SEE GENERAL NOTES #5. PLEASE SEE THIS
 DOES NOT SEEM TO BE ACCURATE FOR THE WORK BEING DONE ON
 THIS PROJECT.
 FBC 106.1.2,NEC 310.16.
  
 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW ONE COPY OF ELECTRICAL PLANS ARE BEING
 RETAINED AND ONE SET OF RED-LINED PLANS WILL GO BACK TO
 CONTRACTOR ONCE ALL REVIEWS ARE DONE.
  
 10) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS /CUT
 SHEETS FOR THE NEW TANK LESS WATER HEATER. PLEASE KNOW
 THIS MUST CONTAIN A LISTING FROM A NRTL. (NATIONALLY
 RECOGNIZED TESTING LABORATORY).
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED, PLEASE KNOW THERE MAY BE COMMENTSON NEXT
 REVIEW.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]