Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 TOILET ROOMS ARE NOT WIDE
 ENOUGH. MINIMUM 5'3" REQUIRED FOR
 ACCESSIBLE TOILET ROOMS.
  
 2. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.3
  
 3. SUBMIT A DETAIL FOR THE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS.
  
 4. SUBMIT A DETAIL FOR THE NEW BATHROOM.
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM
 PLUMBING FIXTURES PER TABLES 1004.1.2
 AND 401.3. INDICATE OCCUPANCY. INDICATE
 AGE AND NUMBER OF STUDENTS.
  
 6. DEMOLITION NOTES ON SHT A-1 INDICATES
 THE CAPING OFF OF PLUMBING. THIS IS NOT
 INDICATED ON THE FLOOR PLAN. PLEASE
 INDICATE WHERE THE PLUMBING PIPES WILL
 BE CAPPED OFF AND BE AWARE THAT DEAD
 ENDS ARE PROHIBITED PER SECTION 704.5.
  
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, TRAPS, VENTS ETC.
 SECTION 106.1.1.
  
 8. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, VALVES, WATER
 HAMMER ARRESTORS (IF REQUIRED BY SECTION
 604.9). SECTION 106.1.1 AND SECTION 606.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]