| 2006-09-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A-1 TOILET ROOMS ARE NOT WIDE |
| | ENOUGH. MINIMUM 5'3" REQUIRED FOR |
| | ACCESSIBLE TOILET ROOMS. |
| | |
| | 2. DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | SECTION 11-4.22.3 |
| | |
| | 3. SUBMIT A DETAIL FOR THE TOILET ROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | |
| | 4. SUBMIT A DETAIL FOR THE NEW BATHROOM. |
| | SHOW COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS. |
| | |
| | 5. SUBMIT CALCULATIONS FOR MINIMUM |
| | PLUMBING FIXTURES PER TABLES 1004.1.2 |
| | AND 401.3. INDICATE OCCUPANCY. INDICATE |
| | AGE AND NUMBER OF STUDENTS. |
| | |
| | 6. DEMOLITION NOTES ON SHT A-1 INDICATES |
| | THE CAPING OFF OF PLUMBING. THIS IS NOT |
| | INDICATED ON THE FLOOR PLAN. PLEASE |
| | INDICATE WHERE THE PLUMBING PIPES WILL |
| | BE CAPPED OFF AND BE AWARE THAT DEAD |
| | ENDS ARE PROHIBITED PER SECTION 704.5. |
| | |
| | 7. SUBMIT A SANITARY RISER ISOMETRIC |
| | DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, TRAPS, VENTS ETC. |
| | SECTION 106.1.1. |
| | |
| | 8. SUBMIT A WATER RISER ISOMETRIC |
| | DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, VALVES, WATER |
| | HAMMER ARRESTORS (IF REQUIRED BY SECTION |
| | 604.9). SECTION 106.1.1 AND SECTION 606. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |