Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-08 00:00:00*****DENIED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) EXITS AND(OR) EXIT ACCESS CORRIDORS
 SHALL REMAIN CLEAR AND UNOBSTRUCTED.
  
 4.) PLEASE INDICATE/DISPLAY/SHOW FIRE
 PROTECTION SYSTEMS (I.E. FIRE ALARM,
 SPRINKLER SYSTEM) ON THE EXIST/NEW FLOOR
 PLAN. HOW WILL THE SCOPE OF WORK AFFECT
 THESE SYSTEMS?
  
 5.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE PROTECTION SYSTEM, PROVIDE SEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS FOR
 REVIEW.
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  