Plan Review Notes
Plan Review Notes For Permit 06081920
Permit Number 06081920
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-07 00:00:00*** UNSAT **
  
 1) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS FOR NEW ELECTRICAL. PLEASE
 CORRELATE WITH A NEW REVISED PANEL
 SCHEDULE TO BE PROVIDED.
 FBC 106.1.2,240.4,310.16
 PLEASE BE SURE TO INDICATE THE CONDUCTOR
 SIZES, OCP ETC.
  
 2) NOTE: PLEASE CLARIFY IF THIS IS A NEW
 USE FOR EDUCATION ? OCCUPANT LOAD,?
 PLACE OF ASSEMBLY?
 FBC 106.1, NFPA-70, ETC.
  
 3) NOTE: PLEASE BE SURE THE PLANS STATE
 THE MIN CODES AS REQUIRED , 2004 FBC,
 2002 NFPA-70, 2002 NFPA-72, AND 2003
 NFPA-101.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  