| Plan Review Notes For Permit 06081912 |
| Permit Number |
06081912 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-11 14:14:38 | *** DENIED *** | | | 1) NEED SIZE OF RETURN AIR DUCT FROM AHU TO | | | 24X24 RHF GRILL, ON PLANS. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY | | | OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|