1 |
|
| Notes |
| Date |
Text |
| 2006-08-31 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PLAN REVIEW: | | | | | | 1. PER FBC-2004 FEUL GAS, SECTION 404.8 | | | PROTECTION AGAINST CORROSION: ZINC | | | COATINGS (GALVANIZING) SHALL NOT BE | | | DEEMED ADEQUATE PROTECTION FOR GAS | | | PIPING UNDERGROUND, AND IS UNACCEPTABLE | | | FOR UNDERGROUND INSTALLATION TO THE CODE | | | OFFICIAL. | | | | | | 2. PLEASE DISTINGUISH ON THE DRAWING | | | EXACTLY WHAT IS NEW PIPE AND WHAT IS | | | EXISTING PIPE. | | | | | | 3. PLEASE NOTE THAT THE GAS PIPE TO THE | | | GENERATOR IS SIZED WRONG, IT SHOULD BE | | | 1" NOT 3/4", PLEASE REFERENCE THE | | | ATTACHED TABLES FOR RESUBMITTAL. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|