Plan Review Notes
Plan Review Notes For Permit 06081900
Permit Number 06081900
Review Stop G
Sequence Number 1
Notes
Date Text
2006-08-31 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. PER FBC-2004 FEUL GAS, SECTION 404.8
 PROTECTION AGAINST CORROSION: ZINC
 COATINGS (GALVANIZING) SHALL NOT BE
 DEEMED ADEQUATE PROTECTION FOR GAS
 PIPING UNDERGROUND, AND IS UNACCEPTABLE
 FOR UNDERGROUND INSTALLATION TO THE CODE
 OFFICIAL.
  
 2. PLEASE DISTINGUISH ON THE DRAWING
 EXACTLY WHAT IS NEW PIPE AND WHAT IS
 EXISTING PIPE.
  
 3. PLEASE NOTE THAT THE GAS PIPE TO THE
 GENERATOR IS SIZED WRONG, IT SHOULD BE
 1" NOT 3/4", PLEASE REFERENCE THE
 ATTACHED TABLES FOR RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721