| Date |
Text |
| 2007-06-28 10:38:02 | REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR |
| | GAS PLAN REVIEW FOR THE REVISION TO MEET CODE |
| | COMPLIANCE: |
| | |
| | 1. NOTE: THE ORIGINAL NATURAL GAS ISOMETRIC RISER |
| | DIAGRAM ON SHEET P-1 WERE SIGNED AND SEALED BY |
| | ARCHITECT KELLY D. YATES, ANY REVISED DRAWING TO THE |
| | GAS SYSTEM PER CHAPTER 481, FLORIDA STATUTES, PART 1, |
| | MUST ALSO BE SIGNED AND SEALED BY SAID DESIGN |
| | PROFESSIONAL. ALSO A TITLE BLOCK IS REQUIRED PER, |
| | FAC-61G1-16.004 TITLE BLOCK: |
| | A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED |
| | SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | (7) FIRMS CERTIFICATE OF AUTHORIZATION NUMBER PER FS |
| | 481.219 |
| | |
| | 2. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE INDICATE |
| | THIS ON THE RESUBMITTED REVISION. |
| | |
| | 3. PLEASE CLEARLY INDICATE THE ABOVE GROUND AND |
| | UNDERGROUND PIPING MATERIAL OF THE GAS SYSTEM. THERE |
| | WAS A REVISION ON THE ORIGINAL DOCUMENTS DATED 3-20-07 |
| | (PLAN REVIEW COMMENTS) IN THE PLUMBING NOTES #5 GAS |
| | PIPING: POLYETHELENE PLASTIC PIPE (PE). PLEASE CLARIFY |
| | THIS ON THE RESUBMITTED REVISION. |
| | |
| | 4. NOTE: THE DRIP LEG DETAIL INDICATED ON THE REVISION |
| | IS WRONG. PLEASE CORRECT THE REVISION PER FBC-2004 FUEL |
| | GAS SECTION 408.4 A SEDIMENT TRAP SHALL BE INSTALLED |
| | DOWNSTREAM OF THE EQUIPMENT SHUTOFF VALVE AS CLOSE TO |
| | THE INLET OF THE EQUIPMENT AS PRACTICAL. A **PROVISO** |
| | WAS PUT ON THE PERMIT COPIES REFLECTING THIS. |
| | |
| | 5. PLEASE PROVIDE TWO COPIES MANUFACTURER'S |
| | SPECIFICATION OF THE MP REGUALTORS WITH THE FOLLOWING |
| | INFORMATION. |
| | A} MAKE. |
| | B} MODEL NUMBER. |
| | C} MAXIMUM INDIVIDUAL LOAD CAPACITY (LARGEST |
| | SINGLE APPLIANCE SERVED BY THE REGULATOR) |
| | D} CAPACITY OF REGULATOR (TOTAL LOAD OF ALL |
| | APPLIANCES COMBINED) |
| | E} SHOW A LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY (NRTL). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |