Plan Review Notes
Plan Review Notes For Permit 06081875
Permit Number 06081875
Review Stop G
Sequence Number 5
Notes
Date Text
2007-06-28 10:38:02REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW FOR THE REVISION TO MEET CODE
 COMPLIANCE:
  
 1. NOTE: THE ORIGINAL NATURAL GAS ISOMETRIC RISER
 DIAGRAM ON SHEET P-1 WERE SIGNED AND SEALED BY
 ARCHITECT KELLY D. YATES, ANY REVISED DRAWING TO THE
 GAS SYSTEM PER CHAPTER 481, FLORIDA STATUTES, PART 1,
 MUST ALSO BE SIGNED AND SEALED BY SAID DESIGN
 PROFESSIONAL. ALSO A TITLE BLOCK IS REQUIRED PER,
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 (7) FIRMS CERTIFICATE OF AUTHORIZATION NUMBER PER FS
 481.219
  
 2. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE INDICATE
 THIS ON THE RESUBMITTED REVISION.
  
 3. PLEASE CLEARLY INDICATE THE ABOVE GROUND AND
 UNDERGROUND PIPING MATERIAL OF THE GAS SYSTEM. THERE
 WAS A REVISION ON THE ORIGINAL DOCUMENTS DATED 3-20-07
 (PLAN REVIEW COMMENTS) IN THE PLUMBING NOTES #5 GAS
 PIPING: POLYETHELENE PLASTIC PIPE (PE). PLEASE CLARIFY
 THIS ON THE RESUBMITTED REVISION.
  
 4. NOTE: THE DRIP LEG DETAIL INDICATED ON THE REVISION
 IS WRONG. PLEASE CORRECT THE REVISION PER FBC-2004 FUEL
 GAS SECTION 408.4 A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE EQUIPMENT SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE EQUIPMENT AS PRACTICAL. A **PROVISO**
 WAS PUT ON THE PERMIT COPIES REFLECTING THIS.
  
 5. PLEASE PROVIDE TWO COPIES MANUFACTURER'S
 SPECIFICATION OF THE MP REGUALTORS WITH THE FOLLOWING
 INFORMATION.
 A} MAKE.
 B} MODEL NUMBER.
 C} MAXIMUM INDIVIDUAL LOAD CAPACITY (LARGEST
 SINGLE APPLIANCE SERVED BY THE REGULATOR)
 D} CAPACITY OF REGULATOR (TOTAL LOAD OF ALL
 APPLIANCES COMBINED)
 E} SHOW A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL).
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved