Plan Review Notes
Plan Review Notes For Permit 06081875
Permit Number 06081875
Review Stop G
Sequence Number 3
Notes
Date Text
2007-02-20 11:46:34DENIED
 REFERENCE: FBC-2004 FUEL GAS AND CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS:
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. OK
  
 2. NO.
 ** SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: SHEET P-1 INDICATES PIPING MATERIAL TO BE
 SCHEDULE 40 BLACK STEEL.
  
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION. FERROUS METAL EXPOSED IN EXTERIOR
 LOCATIONS SHALL BE PROTECTED FROM CORROSION IN A MANNER
 SATISFACTORY TO THE CODE OFFICIAL.
 NOTE: PLEASE ADD TO RESUBMITTED NOTES.
  
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.1 PROHIBIED
 USE, UNCOATED THREADED OR SOCKET WELDED JOINTS SHALL
 NOT BE USED IN PIPING IN CONTACT WITH SOIL OR WHERE
 INTERNAL OR EXTERNAL CREVICE CORROSION IS KNOWN TO
 OCCUR.
 NOTE: PLEASE ADD TO RESUBMITTED NOTES.
  
 C} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING. PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
 NOTE: PLEASE ADD TO RESUBMITTED NOTES.
  
 ** NOTE: IT IS SUGGESTED THAT ANY NEW UNDERGROUNG
 PIPING MATERIAL FOR THE GAS SYSTEM BE POLYETHYLENE
 PLASTIC PIPE (PE). ALSO IF PE PIPE IS USED FOR THE
 GENERATOR THE PIPE SIZE WILL NEED TO BE INCREASED TO
 2-1/2" FOR THE GENERATOR. PLEASE BE AWARE THAT
 UNDERGROUND GALVANIZED PIPE IS UNACCEPTABLE TO THE CODE
 OFFICIAL PER FBC-2004 FUEL GAS, SECTION 404.8.
  
 3. OK
  
 4. OK
  
 5. NO
 ** INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE REFERENCE TO THE FUEL GAS TABLE 402.4 (2) IS
 NOT ACCEPTABLE AS A DELIVERY PRESSURE. DELIVERY
 PRESSURE CAN NOT BE ASSUMED, IT MUST BE CLEARLY
 INDICATED ON THE RESUBMITTAL.
  
 6. OK
  
 7. OK
  
 8. OK
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  