Plan Review Notes
Plan Review Notes For Permit 06081875
Permit Number 06081875
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-03 15:59:24 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHOW THE GROUNDING ELECTRODE SYSTEM CONNECTIONS PER
 250.66. SEE THAT THE LOCATION OF THE ATS NOW MAKES IT
 THE FIRST MEANS OF DISCONNECT., SHOW MAIN BONDING
 JUMPER AND NOTE THAT THE NEUTRAL AND GROUND MUST BE
 ISOLATED BEYOND THAT. ALSO NOTE THAT NO EQUIPMENT
 GROUND IS SHOWN FROM THE SERVICE TO THE GENERATOR WITH
 THAT FEED.
  
 2} THERE MUST BE TWO COPIES OF ALL DOCUMENTS SUBMITTED
 FOR REVIEW, I CAN ONLY FIND ONE OF THE ATS.
  
 3} SECTION 3.2 OF THE ATS MANUAL INDICATES A
 DISCONNECTING MEANS IS REQUIRED AHEAD OF THE ATS FOR
 THE GENERATOR AND UTILITY POWER PRIOR TO MANUAL
 OPERATION. IT DOES NOT APPEAR THIS SWITCH IS RATED AS A
 SERVICE DISCONNECTING MEANS, AND THEREFORE SHOULD NOT
 BE POSITIONED IN THE SERVICE AS SHOWN.
  
 4} PLEASE CALCULATE THE SERVICE LOAD PER 220 SECTION I,
 STANDARD, OR 220 SECTION III, OPTIONAL. DEMANDS CANNOT
 BE REVIEWED FOR COMPLIANCE UNDER THE FORMAT THAT WAS
 SUBMITTED ON THIS PLAN.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.