| Plan Review Notes For Permit 06081875 |
| Permit Number |
06081875 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-03 15:59:24 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} SHOW THE GROUNDING ELECTRODE SYSTEM CONNECTIONS PER | | | 250.66. SEE THAT THE LOCATION OF THE ATS NOW MAKES IT | | | THE FIRST MEANS OF DISCONNECT., SHOW MAIN BONDING | | | JUMPER AND NOTE THAT THE NEUTRAL AND GROUND MUST BE | | | ISOLATED BEYOND THAT. ALSO NOTE THAT NO EQUIPMENT | | | GROUND IS SHOWN FROM THE SERVICE TO THE GENERATOR WITH | | | THAT FEED. | | | | | | 2} THERE MUST BE TWO COPIES OF ALL DOCUMENTS SUBMITTED | | | FOR REVIEW, I CAN ONLY FIND ONE OF THE ATS. | | | | | | 3} SECTION 3.2 OF THE ATS MANUAL INDICATES A | | | DISCONNECTING MEANS IS REQUIRED AHEAD OF THE ATS FOR | | | THE GENERATOR AND UTILITY POWER PRIOR TO MANUAL | | | OPERATION. IT DOES NOT APPEAR THIS SWITCH IS RATED AS A | | | SERVICE DISCONNECTING MEANS, AND THEREFORE SHOULD NOT | | | BE POSITIONED IN THE SERVICE AS SHOWN. | | | | | | 4} PLEASE CALCULATE THE SERVICE LOAD PER 220 SECTION I, | | | STANDARD, OR 220 SECTION III, OPTIONAL. DEMANDS CANNOT | | | BE REVIEWED FOR COMPLIANCE UNDER THE FORMAT THAT WAS | | | SUBMITTED ON THIS PLAN. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|