| Plan Review Notes For Permit 06081875 |
| Permit Number |
06081875 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-14 00:00:00 | | | | | | | NONCOMPLIANT. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, | | | DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN | | | BE REVIEWED. | | | | | | 2} PROVIDE A RISER DIAGRAM SHOWING | | | ELECTRICAL CONNECTION OF ALL SERVICE AND | | | GENERATOR EQUIPMENT. | | | | | | 3} PROVIDE MANUFACTURERS | | | SPECIFICATIONS/RECOMMENDATION, REGARDING | | | CLEARANCES. | | | | | | 4} PROVIDE SPECIFICATIONS FOR THE | | | TRANSFER SWITCH. | | | | | | 5} PROVIDE A CALCULATION FOR THE LOAD | | | BEING SERVED BY THE GENERATOR. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | |
|