2006-10-29 06:32:18*****REDLINED PLANS *****
  
  
 1) DISCONNECT FOR TRANSFORMER REDLINED ON E-1.1 TO SEE
 RISER FOR DISCONNETC PER 240.21
  
 2) DEVICES NOW BEING NOTED ON E-2.1 NOTE TO THE SOUTH
 FLORIDA BUILFING CODE?, CHANGED TO "FBC".SFBC IS NO
 LONGER IN EFFECT.
 ALSO REDLINED THE MAXIMUM OF 30MINS OVER RIDE TIMES FOR
 OCC SENSOR TYPE DEVICES AS REQUIRED PER
 13-415.1.ABC.1.1
 PREVIOUS NOTE.
  
  
 NO CHANGES ARE REQUIRED TO BE MADE TO PLANS, ONLY MAKE
 ADJUSTMENTS IF REVISING PLANS DURINGCONSTRUCTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  