| Plan Review Notes For Permit 06081871 |
| Permit Number |
06081871 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-29 06:32:18 | *****REDLINED PLANS ***** | | | | | | | | | 1) DISCONNECT FOR TRANSFORMER REDLINED ON E-1.1 TO SEE | | | RISER FOR DISCONNETC PER 240.21 | | | | | | 2) DEVICES NOW BEING NOTED ON E-2.1 NOTE TO THE SOUTH | | | FLORIDA BUILFING CODE?, CHANGED TO "FBC".SFBC IS NO | | | LONGER IN EFFECT. | | | ALSO REDLINED THE MAXIMUM OF 30MINS OVER RIDE TIMES FOR | | | OCC SENSOR TYPE DEVICES AS REQUIRED PER | | | 13-415.1.ABC.1.1 | | | PREVIOUS NOTE. | | | | | | | | | NO CHANGES ARE REQUIRED TO BE MADE TO PLANS, ONLY MAKE | | | ADJUSTMENTS IF REVISING PLANS DURINGCONSTRUCTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-10-29 05:59:21 | IN ELEC FOR REVIEW, WILL PROCESS BACK TO INCOMING WHEN | | | COMPLETED. |
|