| 2006-10-20 19:57:29 | ****UNSAT2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW INCLUDING |
| | NEW NOTES DUE TO SOME CHANGES IN PLANS. |
| | PLEASE SEE NEW NOTES BELOW ADDED TO BOTTOM OF REVIEW. |
| | |
| | 1) NOTE:OK, ADDRESS CHANGED TO # 138 |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE:OK, HOWEVER PLEASE SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY THE LOCATION OF |
| | THE EXISTING TRANSFORMER ON PLANS. RISER |
| | SEEMS TO SHOW THIS ELEVATED WHICH IS OK, |
| | HOWEVER THIE SHALL NOT BE INSTALLED |
| | ABOVE CEILING(S)/HOLLOW SPACES PER |
| | 450.13B |
| | ** PLEASE BE AWARE, THE ORIGINAL PLANS |
| | FOR THE BUILT OUT OF THIS SPACE DID NOT |
| | SHOW THE UNIT ABOVE THE CEILING OR |
| | INSTALLED IN ANY HOLLOW SPACE. |
| | |
| | 4) NOTE:NO, PLEASE SEE PLANS ON "A" SHEET NOWS |
| | INDICATES A 2004 NEC. PLEASE KNOW, THIS SHEET DOES NOT |
| | NEED TO BE CHANGEDAS THIS CAN BE REDLINED BY THE |
| | REVIEWER IF GRANTED PERMISSION BY THE ARCHITECT OF |
| | RECORD.(2002 NEC) |
| | |
| | ** PREVIOUSREVIEW NOTE ** |
| | PLEASE SEE "A" SHEETS SHALL |
| | INDICATE THE LATEST ADOPTED CODES |
| | RELEVANT TO DESIGN AND SCOPE OF WORK. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: NO, PLEASE CLARIFY WHERE THE OVER RIDE DEVICE |
| | IS LOCATED AT THE NEAREST POINT OF ENTRANCE INTO THE |
| | SPACE AND SO THAT THE OCCUPANT CAN VISUALLY SEE THE |
| | LIGHTING WHICH IS BEING CONTROLLED. |
| | PLEASE SEE EXSITNG ROOMS CONTAINING FLR TO CEILING |
| | HEIGHT PARTIONS/WALLS. |
| | PLEASE VERIFY THESE DEVICES. |
| | 13-415.10ABC0101, .1.2 |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THAT EXISTING AREAS |
| | OF OFFICE, BATHRMS, AND AREAS IN THE |
| | REAR OF SPACE WILL ALSO BE REQUIRED TO |
| | HAVE CONTROLSFOR LIGHTING MEETING FBC |
| | 2004 CHAPTER 13. |
| | PLEASE ADJUST. |
| | PLEASE SEE THAT SPEARATE SPACES WHICH |
| | REQUIRE CONTROLS WHICH OVER RIDE THE |
| | LIGHTING CONTROL SYSTEM, AS WELL AS THE |
| | POINT OF ENTRANCE INTO THE SPACE. |
| | |
| | |
| | ** NEW NOTE *** |
| | |
| | 7) NOTE: PLEASE SEE THE LOCATION OF THE TRANSFORMER IS |
| | NOW BRING MOVED TO CORRECT THE EXSITING CODE VIOLATION, |
| | HOWEVER PLEASE SEE THE LOCATION IS SHOWN FARTHER AWAY |
| | FROM THE PANEL"LB"WHICH NOW APPEARS TO CREATE AN |
| | ISSUE WITH 240.21C. PLEASE SEE LENGTH OF TAPPED |
| | CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER |
| | SHALL TERMINATE IN OCP DEVICE WITHIN THE MAXIMUM LIMITS |
| | OF THE "CONDUCTOR" LENGTH. |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS. THIS IS ONLY |
| | A NOTICE GIVEN AT THIS TIME. |
| | AS REQUIRED. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |