Plan Review Notes
Plan Review Notes For Permit 06081871
Permit Number 06081871
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-20 19:57:29****UNSAT2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW INCLUDING
 NEW NOTES DUE TO SOME CHANGES IN PLANS.
 PLEASE SEE NEW NOTES BELOW ADDED TO BOTTOM OF REVIEW.
  
 1) NOTE:OK, ADDRESS CHANGED TO # 138
  
 2) NOTE: OK.
  
 3) NOTE:OK, HOWEVER PLEASE SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE LOCATION OF
 THE EXISTING TRANSFORMER ON PLANS. RISER
 SEEMS TO SHOW THIS ELEVATED WHICH IS OK,
 HOWEVER THIE SHALL NOT BE INSTALLED
 ABOVE CEILING(S)/HOLLOW SPACES PER
 450.13B
 ** PLEASE BE AWARE, THE ORIGINAL PLANS
 FOR THE BUILT OUT OF THIS SPACE DID NOT
 SHOW THE UNIT ABOVE THE CEILING OR
 INSTALLED IN ANY HOLLOW SPACE.
  
 4) NOTE:NO, PLEASE SEE PLANS ON "A" SHEET NOWS
 INDICATES A 2004 NEC. PLEASE KNOW, THIS SHEET DOES NOT
 NEED TO BE CHANGEDAS THIS CAN BE REDLINED BY THE
 REVIEWER IF GRANTED PERMISSION BY THE ARCHITECT OF
 RECORD.(2002 NEC)
  
 ** PREVIOUSREVIEW NOTE **
 PLEASE SEE "A" SHEETS SHALL
 INDICATE THE LATEST ADOPTED CODES
 RELEVANT TO DESIGN AND SCOPE OF WORK.
 106.1.2 FBC ADMIN SECT.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE CLARIFY WHERE THE OVER RIDE DEVICE
 IS LOCATED AT THE NEAREST POINT OF ENTRANCE INTO THE
 SPACE AND SO THAT THE OCCUPANT CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE SEE EXSITNG ROOMS CONTAINING FLR TO CEILING
 HEIGHT PARTIONS/WALLS.
 PLEASE VERIFY THESE DEVICES.
 13-415.10ABC0101, .1.2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT EXISTING AREAS
 OF OFFICE, BATHRMS, AND AREAS IN THE
 REAR OF SPACE WILL ALSO BE REQUIRED TO
 HAVE CONTROLSFOR LIGHTING MEETING FBC
 2004 CHAPTER 13.
 PLEASE ADJUST.
 PLEASE SEE THAT SPEARATE SPACES WHICH
 REQUIRE CONTROLS WHICH OVER RIDE THE
 LIGHTING CONTROL SYSTEM, AS WELL AS THE
 POINT OF ENTRANCE INTO THE SPACE.
  
  
 ** NEW NOTE ***
  
 7) NOTE: PLEASE SEE THE LOCATION OF THE TRANSFORMER IS
 NOW BRING MOVED TO CORRECT THE EXSITING CODE VIOLATION,
 HOWEVER PLEASE SEE THE LOCATION IS SHOWN FARTHER AWAY
 FROM THE PANEL"LB"WHICH NOW APPEARS TO CREATE AN
 ISSUE WITH 240.21C. PLEASE SEE LENGTH OF TAPPED
 CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER
 SHALL TERMINATE IN OCP DEVICE WITHIN THE MAXIMUM LIMITS
 OF THE "CONDUCTOR" LENGTH.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS. THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
 AS REQUIRED.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  