2006-08-25 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE ISOMETRIC
 DRAWING FOR A GAS PERMIT:
  
 1. TYPE OF GAS, (LP OR NATURAL)
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.IF GAS
 SYSTEM IS 2LB SUBMIT MANUFACTURER CUT
 SHEETS OF REGULATORS AND LOCATE THE
 REGULATORS ON THE ISOMETRIC DRAWING.
  
 4. PER FBC-2004 CHAPTER 1, SEC. 106
 CONSTRUCTION DOCUMENTS SUBMITTED IN
 PENCIL ARE UNACCEPTABLE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  