| 2006-08-25 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PLAN REVIEW ON THE ISOMETRIC | | | DRAWING FOR A GAS PERMIT: | | | | | | 1. TYPE OF GAS, (LP OR NATURAL) | | | | | | 2. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2.IF GAS | | | SYSTEM IS 2LB SUBMIT MANUFACTURER CUT | | | SHEETS OF REGULATORS AND LOCATE THE | | | REGULATORS ON THE ISOMETRIC DRAWING. | | | | | | 4. PER FBC-2004 CHAPTER 1, SEC. 106 | | | CONSTRUCTION DOCUMENTS SUBMITTED IN | | | PENCIL ARE UNACCEPTABLE. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | | | | | | | |
|