Plan Review Notes
Plan Review Notes For Permit 06081714
Permit Number 06081714
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-23 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN
 EXTRACTION FROM THE EXEMPTION IN CHAPTER
 471 OF THE FLORIDA STATUTES , 471.003,
 ALLOWING THE CONTRACTOR TO DRAW THEIR
 OWN PLANS.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225.31-39,
 230.70 AND 230.72 CAN BE REVIEWED.
  
 3} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH, INDICATING NUMBER OF
 POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE
 DISCONNECTED.
  
 4} INDICATE THE VOLTAGE OF THE SERVICE.
 NOTE: IF OVER 240 VOLTS, PLANS MUST BE
 ENGINEERED PER CHAPTER 471 FS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  