Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop G
Sequence Number 4
Notes
Date Text
2007-08-17 07:58:30 
  
 PASSED/PROVISO
  
 1. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION). THIS IS OK PROVIDING: 301.5
 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. OK
 8. OK
  