Text |
| 2007-07-13 08:41:08 | 2007-07-13 08:41:08 |
| | |
| | ** UNSAT 4TH REVIEW** |
| | |
| | 1) NOTE:PLEASE SEE THE PREVIOUS COMMENTS REQUESTED |
| | THE ENERGY CALCULATIONS WHICH WERE SUBMITTED TO |
| | COORDINATE WITH THE ELECTRICAL PLANS. THERE WAS NO |
| | COMMENT THAT THE VERSION OF THE CALCULATIONS NEEDED TO |
| | CHANGE. |
| | PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED IS |
| | VERSION 3.0 WHICH WENT INTO EFFECT DECEMBER 8TH, 2006. |
| | PLEASE KNOW HOWEVER AS THIS PROJECT WAS SUBMITTED UNDER |
| | THE PREVIOUS CODE BEFORE THE CODE CHANGE OF DECEMBER |
| | 8TH, 2006, THE CALCULATIONS NEED TO BE DONE UNDER THE |
| | PREVIOUS 2.11 AS SUBMITTED UNDER THE PREVIOUS REVIEW. |
| | PLEASE BE SURE TO TRANSFER ALL INFORMATION OVER TO THE |
| | CALCULATIONS. |
| | PLEASE SEE THE PREVIOUS CALCULATIONS SUBMITTED |
| | INDICATED 1750 SQ FT AND NOW THE NEW ONES INDICATE 2970 |
| | SQ FT? PLEASE BE SURE THE CALCULATIONS COORDINATE WITH |
| | PLANS AND THE CORRECT VERSION. |
| | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL. |
| | |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-07 14:54:06 | 2007-07-07 14:54:06 |
| | |
| | |
| | CONTRACTOR CAME IN AND CORRECTED SETS FOR REVIEW ON |
| | 7/11 |
| 2007-07-07 14:34:21 | 2007/07/07 14:34:21 |
| | PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| | IS COMPLETED. |