2007-07-25 17:45:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)A SITE PLAN WAS PROVIDED IN RESPONSE TO CORRECTION
 #7, A REQUEST FOR A SURVEY TO DETERMINE COMPLIANCE WITH
 FBC TABLE 602.A SITE PLAN WAS PROVIDED, BUT IT SHOWS
 A SECTION OF THE BUILDING HATCHED WHICH ENCROACHES THE
 PROPERTY LINE.DOES THIS BUILDING ENCROACH THE
 PROPERTY LINE?NORTH ON THE SITE PLAN DOES NOT
 CORRELATE WITH THE NORTH ON THE FLOOR PLAN.IT APPEARS
 THAT NORTH ON THE FLOOR PLAN IS ACTUALLY WEST.IT
 APPEARS THAT THE WEST AND NORTH ELEVATIONS OF THE
 BUILDING ARE ON THE PROPERTY LINE, REQUIRING A 3 HOUR
 FIRE RATING FBC TABLE 602.NOTE THAT THE FEC EASEMENT
 IS NOT CONSIDERED OPEN SPACE.TYPE IIIB REQUIRES 2
 HOUR BEARING WALLS FBC TABLE 601.
  
 THE SITE PLAN IS NOT LEGIBLE.PROVIDE A COPY OF THE
 SURVEY AS REQUESTED WHICH WILL CLEARLY SHOW THE
 BUILDING FOOTPRINT IN RELATION TO THE PROPERTY LINE.
  
 2.)SEE ELECTRIC COMMENTS REGARDING THE ENERGY CALCS.
  
  
  
  