Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop P
Sequence Number 3
Notes
Date Text
2007-06-06 14:47:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. THE TWO PAGE "WORKSHEET" FROM DBPR
 PLAN REVIEW SHALL BE ATTACHED TO EACH
 SET OF PLANS. SECTION 106.1.3.
 ****NOT ADDRESSED, AND NOW THE DBPR STAMPED SHEETS ARE
 NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE
 STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG
 WITH THE TWO PAGE "WORKSHEETS".
 ********COMMENT NOT ADDRESSED. PLEASE SUBMIT A MINIMUM
 OF TWO SETS OF PLANS FOR REVIEW WILL ALL REQUIRED
 SHEETS.
  
 7. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION)
 301.5 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF
 VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS
 REQUIRED.
 ********NOW MANUAL VALVE IS LOCATED DOWNSTREAM OF THE
 AUTOMATIC SHUT OFF VALVE. PLEASE SHOW THE MANUAL VALVE
 UPSTREAM OF THE AUTOMATIC VALVE.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved