| | ** UNSAT3RD REVIEW** |
| | |
| | 1) NOTE: PLEASE SEE THEAIC RATINGS SHOW DIFFERENT |
| | LENGTHS ON PLANS FROM THE ACTUAL LENGTHS SHOWN ON |
| | SHEETS WHERE CONDUITS ARE RUN. |
| | PLEASE SEE THE LENGTH SHOWN AS 60FT IS ACTUALLY LONGER |
| | BY WHAT IS BEING SHOWN ON PLANS. |
| | THE AVAILABLE FAULT CURRENT WILL ACTUALLY BE LESS. |
| | 110.9, |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE VERIFY VOLTAGE DROP FOR THESE SAME |
| | SERVICE CONDUCTORS AS THE LENGTH ON PLANS IS LONGER |
| | THAN FIGURES. |
| | 13-413. |
| | |
| | 3) NOTE: PLEASE SEE THE SAME ENERGY CALCULATIONS WERE |
| | SUBMITTED BACK AS SUBMITTED ON PREVIOUS SUBMITTAL. |
| | PLEASE SEE THE LIGHTING ON CALCULATIONS DO NOT |
| | CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF |
| | FIXTURES AND WATTAGE. ONLY ONE FIXTURE IS NOTED ON |
| | CALCULATIONS. |
| | PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ALSO |
| | INDICATE MANUAL MEANS FOR CONTROL OF LIGHTING WHEN THE |
| | PLANS INDICATE AUTOMATED MEANS. |
| | PLEASE ADJUST. |
| | PLEASE ALSO SEE THE SHEETS WHICH ARE REQUIRED TO BE |
| | SIGNED DATED AND SEALED NEEDS TO BE THE SHEETS WHICH |
| | CONTAIN THE LICENSEE INFORMATION. (2ND SHEET IN). |
| | PLEASE SEE THE METHOD AS SHOWN ON PLANS IS *B*, YET |
| | ENERGY CALCULATIONS ARE *A*.? |
| | PLEASE COORDINATE. |
| | 13-415.1.A, 13-415.1.B, 13-415.C, 13-415.2 |
| | 13-103.1.1.1 |
| | |
| | 4) NOTE: PLEASE CLARIFY HOW MANY MAINS ARE ON THE |
| | EXISTING SERVICE AND LABEL MAINS , 1OF ? , 2OF ? ETC. |
| | 230.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |