Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-25 13:33:06 
  
 ** UNSAT3RD REVIEW**
  
 1) NOTE: PLEASE SEE THEAIC RATINGS SHOW DIFFERENT
 LENGTHS ON PLANS FROM THE ACTUAL LENGTHS SHOWN ON
 SHEETS WHERE CONDUITS ARE RUN.
 PLEASE SEE THE LENGTH SHOWN AS 60FT IS ACTUALLY LONGER
 BY WHAT IS BEING SHOWN ON PLANS.
 THE AVAILABLE FAULT CURRENT WILL ACTUALLY BE LESS.
 110.9,
 FBC 106.1.2
  
 2) NOTE: PLEASE VERIFY VOLTAGE DROP FOR THESE SAME
 SERVICE CONDUCTORS AS THE LENGTH ON PLANS IS LONGER
 THAN FIGURES.
 13-413.
  
 3) NOTE: PLEASE SEE THE SAME ENERGY CALCULATIONS WERE
 SUBMITTED BACK AS SUBMITTED ON PREVIOUS SUBMITTAL.
 PLEASE SEE THE LIGHTING ON CALCULATIONS DO NOT
 CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF
 FIXTURES AND WATTAGE. ONLY ONE FIXTURE IS NOTED ON
 CALCULATIONS.
 PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ALSO
 INDICATE MANUAL MEANS FOR CONTROL OF LIGHTING WHEN THE
 PLANS INDICATE AUTOMATED MEANS.
 PLEASE ADJUST.
 PLEASE ALSO SEE THE SHEETS WHICH ARE REQUIRED TO BE
 SIGNED DATED AND SEALED NEEDS TO BE THE SHEETS WHICH
 CONTAIN THE LICENSEE INFORMATION. (2ND SHEET IN).
 PLEASE SEE THE METHOD AS SHOWN ON PLANS IS *B*, YET
 ENERGY CALCULATIONS ARE *A*.?
 PLEASE COORDINATE.
 13-415.1.A, 13-415.1.B, 13-415.C, 13-415.2
 13-103.1.1.1
  
 4) NOTE: PLEASE CLARIFY HOW MANY MAINS ARE ON THE
 EXISTING SERVICE AND LABEL MAINS , 1OF ? , 2OF ? ETC.
 230.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  