Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop B
Sequence Number 3
Notes
Date Text
2007-05-08 09:44:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM THE PREVIOUS LISTS, NUMBERING REMAINING THE SAME
 FOR CONSISTENCY:
  
 1.)ADDRESSED.
  
 2.)AS AGREED, THIS IS A CHANGE OF OCCUPANCY.PLEASE
 INCLUDE THIS INFORMATION (CHANGE OF OCCUPANCY) IN THE
 BUILDING CODE CHECKLIST AS THE CHANGE OF OCCUPANCY
 REQUIRES COMPLIANCE WITH ALL REQUIREMENTS OF FBC EB
 CHAPTER 8.SOME COMMENTS ARE DUE TO THE CHAPTER 8
 REQUIREMENTS.
 7.)PROVIDE A SURVEY FOR THIS PROPERTY
 TO DETERMINE COMPLIANCE WITH FBC TABLE
 602.
  
 8.)1ST REVIEW COMMENT - THE NORTH WALL APPEARS TO BE
 A
 TENANT SEPARATION WALL; WHAT OCCUPANCY CLASSIFICATION
 IS THAT SPACE?SHOW
 COMPLIANCE WITH FBC TABLE 302.3.2.
  
 2ND REVIEW COMMENT - THE PLAN WAS REVISED TO SHOW B
 OCCUPANCY.NO COMPLIANCE WITH FBC TABLE 302.3.2
 SHOWN.
  
 3RD REVIEW COMMENT - AS DISCUSSED, IF THIS IS A
 SEPARATED USE FBC302.3.2, A 3 HOUR OCCUPANCY SEPARATION
 IS REQUIRED BETWEEN B AND F1, FBC TABLE 302.3.2.IF
 THIS IS A NON SEPARATED USE FBC302.3.1, YOU MUST SHOW
 COMPLIANCE WITH THE MOST STRINGENT OCCUPANCY FBC TABLE
 503, FBC TABLE 601, FBC TABLE 602.IF ALLOWABLE AREA
 INCREASES ARE USED, SHOW ALL CALCULATIONS ON THE PLAN.
 CODE COMPLIANCE IS TO BE CLEAR AND IS TO BE
 INCORPORATED INTO THE PLAN (CANNOT BE ADDRESSED THROUGH
 A RESPONSE LETTER).
  
 WHEN SHOWING REQUIRED FIRE RESISTANCE, EITHER SPECIFY
 AN APPROVED LISTING OR CALCULATED FIRE RESISTANCE
 (LISTING ALL COMPONENTS AS WELL AS TIME ASSIGNED TO
 EACH COMPONENT), FBC CHAPTER 7.
  
 10.)PROVIDE OVERALL DIMENSIONS OF THE
 SPACE ON THE LIFE SAFETY SHEET A120.1. (NOT ADDRESSED.
 OVERALL DIMENSIONS ARE NOT SHOWN ON ANY OF THE FLOOR
 PLANS PROVIDED.)
  
 11.)SEE FBC306.2.FOOD PROCESSING IS
 FACTORY OCCUPANCY CLASSIFICATION.
 CLARIFY WHY YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE FOOD PROCESSING AREA.
 SEE FBC302.1, PORTIONS OF STRUCTURES ARE
 TO BE CLASSIFIEDWITH RESPECT TO
 OCCUPANCY.
  
 3RD REVIEW - NOT ADDRESSED.PER MY CONVERSATION WITH
 THE ARCHITECT, THE FOOD IS PREPARED AND SERVED HOT AT
 ANOTHER LOCATION.DESPITE THIS ADDITIONAL INFORMATION
 (THE FACT THAT THE FOOD LEAVES THE FACILITY HOT RATHER
 THAN COLD), I THINK THAT THE CORRECT OCCUPANCY
 CLASSIFICATION IS F1, FBC306.2.ARCHITECT IS TO EITHER
 REVISE THE OCCUPANCY CLASSIFICATION ON THE PLAN AND
 SHOW CODE COMPLIANCE OR SUBMIT JUSTIFICATION (IN
 WRITING, PRIOR TO THE NEXT RESUBMITTAL) FOR THE
 BUSINESS OCCUPANCY DECLARED TO BE REVIEWED BY ASSISTANT
 BUILDING OFFICIAL.AS DISCUSSED IN OUR TELEPHONE
 CONVERSATION, IT APPEARS THAT A NON SEPARATED USE
 FBC302.3.1 MAY BE AN OPTION.
  
 16.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-103.1.
  
 3RD REVIEW - THE PREPARER AND OWNER AGENT ARE TO SIGN
 THE ENERGY CALCS.
  
 17.)THE SQUARE FOOT AREA ON THE ENERGY
 CALC DOES NOT MATCH THE PLAN.NO
 UNCONDITIONED AREA SHOWN ON THE ENERGY
 CALC, UNCONDITIONED AREA SHOWN ON PLAN.
  
 3RD REVIEW - PLEASE DECLARE TOTAL SF AREA FOR THE
 TENANT SPACE, BOTH CONDITIONED AND UNCONDITIONED.WHEN
 SCALED, THE AREA IS APPROXIMATELY 1568 SQUARE FEET.
 ENERGY CALCS STATE 1750 CONDITIONED, 1750
 CONDITIONED/UNCONDITIONED.OCCUPANT LOAD IS 30 AT
 100SF PER PERSON.CODE COMPLIANCE WITH OCCUPANT LOAD
 AND EGRESS REQUIREMENTS CANNOT BE DETEREMINED DUE TO
 INSUFFICIENT/INCOMPLETE/INCONSISTENT INFORMATION.
  
 THE ENERGY CALCS DID NOT PASS ELECTRIC REVIEW.NOTE
 THAT ENERGY CALCS ARE REQUIRED; CORRECT, CODE COMPLIANT
 ENERGY CALCS ARE REQUIRED FOR PERMIT ISSUANCE.
 STATUTORY REQUIREMENTS CAN NEVER BE WAIVED OR
 PROVISO'D.
  
 18.)INTERIOR FINISHES TO COMPLY WITH TABLE 803.5.
  
 3RD REVIEW - THIS WAS ADDRESSED ON SHEET A130. HOWEVER,
 THE ARCHITECT HAS DECLARED BUSINESS OCCUPANCY BUT THE
 INTERIOR FINISHES REQUIREMENTS DO NOT COMPLY WITH TABLE
 803.5 FOR BUSINESS OCCUPANCY, BUT ARE COMPLIANT FOR
 F1.
  
 19.)SEE ATTACHED FS 553.80(2)(B).
  
 3RD REVIEW - DUE TO SEVERAL OF THE ABOVE COMMENTS, A 4X
 PLAN REVIEW FEE HAS BEEN ASSESSED AS REQUIRED BY
 FLORIDA STATUTE.A BILL IS ATTACHED AND MUST BE PAID
 WHEN RESUBMITTING.
  
 18.)PROVIDE INFORMATION IN REGARDS TO ACCESSIBLE
 PARKING, ACCESSIBLE ROUTE.SEE FBC11-4.1.4.6(2).
  
 3RD REVIEW - SEE ATTACHED DETAIL WHICH IS THE CITY OF
 WEST PALM BEACH STANDARD PARKING DETAIL AND REVISE
 A110.1.ALSO SHOW THE ACCESSIBLE ROUTE; FROM THE
 PUBLIC WAY, AND FROM THE ACCESSIBLE PARKING.THIS CAN
 BE DONE ON THE SITE PLAN.
  