| Date |
Text |
| 2006-12-07 06:36:13 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | |
| | 1. PER TABLES 1004.1.2 AND 403.1 2-W/C'S |
| | AND SEPARATE FACILITIES ARE REQUIRED. - |
| | ALSO A DRINKING FOUNTAIN IS REQUIRED. |
| | ****RESPONSE NOTED, BUT NO DRINKING FOUNTAIN PROVIDED. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(2) A |
| | BUSINESS NUMBER IS REQUIRED. FS 481.219. ****RESPONSE |
| | NOTED, BUT THE GENERAL NOTES REFER TO RJS ARCHITECTS |
| | INC. IN NOTES 1, (TWICE), 4, & 8. ALL REFERENCES TO RJS |
| | ARCHITECTS INC. SHALL BE DELETED FROM PLANS OR A |
| | BUSINESS NUMBER WILL BE REQUIRED. |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | |
| | 6. THE TWO PAGE "WORKSHEET" FROM DBPR |
| | PLAN REVIEW SHALL BE ATTACHED TO EACH |
| | SET OF PLANS. SECTION 106.1.3. |
| | ****NOT ADDRESSED, AND NOT THE DBPR STAMPED SHEETS ARE |
| | NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE |
| | STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG |
| | WITH THE TWO PAGE "WORKSHEETS". |
| | |
| | 7. SHT P-1 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. OK |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS |
| | USED AND WILL BE MOVED FROM AN EXISTING CATERING |
| | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT |
| | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE |
| | FOLLOWING CODE SECTION) |
| | 301.5 LABEL INFORMATION. |
| | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE |
| | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE |
| | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE |
| | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, |
| | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL |
| | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS |
| | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE |
| | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE |
| | REQUIREMENTS. |
| | |
| | |
| | C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN |
| | ON THE GAS ISOMETRIC RISER DIAGRAM. |
| | ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF |
| | VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS |
| | REQUIRED. |
| | |
| | 8. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |