| 2006-11-01 09:39:37 | DENIED: |
| | PLEASE PROVIDE A SURVEY OF THE PROPERTY. |
| | |
| | 1.THE 8" EXHAUST, DRYWELL & GAS METER ARE ALL LOCATED |
| | ON THE SOUTH WALL WHICH APPEARS TO BE A ZERO LOT LINE. |
| | |
| | PROVISO: |
| | 1.DETAIL OF THE ROOF MOUNTED |
| | CONDENSING UNIT SHOWN ON PLAN SHEET M-2 |
| | DOES NOT INDICATE CLEARANCE BETWEEN THE |
| | ROOF AND STAND AS REQUIRED PER 2004 FBC |
| | TABLE 1509.7 |
| | |
| | 2.MAKEUP AIR FOR THE KITCHEN SHALL |
| | COMPLY WITH 2004 FMC 508.1. |
| | |
| | 3.ADDITIONAL PERMITS REQUIRED FOR THE |
| | HOOD, FIRE SUPPRESSION AND WALK-IN |
| | COOLERS.PLEASE PROVIDE PLANS AND |
| | MANUFACTURER'S SUBMITTAL DATA.PLEASE |
| | INDICATE THE FOLLOWING INFORMATION WITH |
| | REGARDS TO THE HOOD: |
| | A) TERMINATION OF EXHAUST. PROVIDE |
| | DISTANCE TO PROPERTY LINES, PARAPITS, |
| | ADJOING BUILDINGS, INTAKE OPENINGS, |
| | ETC. |
| | B) PROVIDE EQUIPMENT SCHEDULE FOR THE |
| | EXHAUST FAN. |
| | C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL |
| | D) VELOCITY THROUGH DUCT SHALL BE A |
| | MINIMUM OF 1,500 FPM BUT NOT GREATER |
| | THAN 2,500 FPM. |
| | E) INDICATE CLEARANCES TO COMBUSTIBLES. |
| | D) PROVIDE DETAIL FOR THE HANGING & |
| | VIBRATION ISOLATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719 OR |
| | E-MAIL [email protected]. |