| Date |
Text |
| 2006-10-27 16:25:55 | *** UNSAT2ND REVIEW****** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW AND |
| | SOME NEW COMMENTS DUE TO THE PLANS SUBMITTED. |
| | PLEASE SEE NOTES BELOW WHICH ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW. |
| | |
| | 1) NOTE: OK, HOWEVER PLEASE BE SURE TO CORRECT PERMIT |
| | APPLICATION AS ADDRESS STILLS SHOWS 6600. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PERMIT APPLICATION |
| | DOES NOT MATCH WITH THE LEGAL OWNER OF |
| | RECORD ON OUR SYSTEM, THE PALM BEACH |
| | COUNTY PROPERTY APPRAISER'S WEBSITE OR |
| | THE NOTICE OF COMMENCEMENT SUBMITTED. |
| | PLEASE CORRECT AND REVISE. |
| | |
| | |
| | 2) NOTE: OK. NOTE #1 |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE:NO, PLEASE SEE AS SHOWN ON PLANS , THIS IS |
| | "NOT" CLASSIFIED AS SEPARATE BUILDING BY RATING THE |
| | WALL 4HRS. PLEASE SEE DEFINITION OF "FIRE WALL " IN THE |
| | FBC. |
| | ONE SERVICE OR COMING FROM THE EXISTING SERVICE OR |
| | MEETING AN EXCEPTION. PLEASE KNOW, AS SHOWN IN ORDER |
| | FOR THIS OFFICE TO GRANT SPECIAL PERMISSION, PLEASE |
| | CALL TO GO OVER. PLEASE KNOW A PHONE MEETING WITH THE |
| | ENGINEER OF RECORD WOULD BE RECOMMEND AND POSSIBLY THE |
| | ARCHITECT TO RESOLVE THIS MATTER MAY BE NEEDED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THIS IS A TENANT |
| | SPACE PART OF A LARGER BUILDING AND THE |
| | NEW SERVICE AS SHOWN IS NOT GRANTED OR |
| | PERMITTED. 230.2 |
| | ** PLEASE SEE AERIAL MAP PROVIDED. |
| | PLEASE SEE SERVICE LOCATION FOR THE |
| | EXISTING SERVICE IS TO BE SHOWN. |
| | PLEASE SEE SERVICE AS SHOWN IS BEING |
| | SHOWN AS AN OVERHEAD SERVICE LOCATED ON |
| | THE SOUTH SIDE OF BUILDING WHERE THE |
| | BUILDING FROM THE ADJOINING PROPERTY IS |
| | LOCATED. CLEARANCES AS REQUIRED UNDER |
| | THE FPL SERVICE GUIDELINES AND NEC ARE |
| | NOTMET IN EITHER CASE. |
| | PLEASE KNOW, THE EXISTING SERVICE FOR |
| | THE BUILDING MUST BE USED OR UPGRADED. |
| | PLEASE SEE THE 1HR SEPARATION DOES NOT |
| | MAKE THIS SPACE A SEPARATE BUILDING. |
| | PLEASE SEE FBC DEFINITIONS OF BUILDING, |
| | AND REQUIRED "FIRE WALL" IN ORDER TO |
| | BECOME A SEPARATE BUILDING. PLEASE SEE |
| | REQUIRED "FIRE WALL" WOULD BE A FOUR HR |
| | RATED WALL WHICH WOULD PERMIT THE |
| | COLLAPSE THE ADJOINING STRUCTURE WITHOUT |
| | AFFECT THE STRUCTURAL INTEGRITY OF THE |
| | ADJOINING REMAINING BUILDING. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE:NO, PLEASE SEE MEANS OF EGRESS INTO ANY ONE |
| | AREA/ KITCHEN ETC WILL REQUIRE A MEANS FOR OVER RIDING |
| | THE TIME OF DAY SCHEDULING.PLEASE SEE REDLINED AREAS |
| | ON PLANS. PLEASE ALSO SEE THAT THE OVER RIDES SWITCH IF |
| | TIMER TYPE IS TO BE SHOWN WITH A MAX OF 4HRS OR IF AN |
| | OCC SENSOR TYPE 30MINS MAX). |
| | PLEASE SEE ENERGY CALCULATIONS ARE NOT SIGNED, DATED |
| | AND SEALED ON THE CORRECT SHEET. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | IF TRYING TO OBTAIN COMPLIANCE |
| | WITH THE 2004 FBC CHAPTER 13,THE |
| | LIGHTING CONTROLS AS NOTED ARE NOT |
| | COMPLETE AT THIS TIME.PLEASE SHOW THE |
| | DETAIL FOR "SYSTEM" BEING PROPOSED. |
| | PLEASE ALSO INCLUDE EXISTING OFFICE |
| | AREAS ARE REQUIRED TO BE CONTROLLED BY |
| | THIS SYSTEM. |
| | PLEASE PROVIDE SCHEDULING, OVER RIDE |
| | DEVICES ALONG WITH MAX PERMITTED TIMES |
| | ON OVER RIDE DEVICES. |
| | (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON |
| | OCCUPANT SENSOR TYPES). |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND |
| | .1.3. |
| | |
| | 7) NOTE: ?? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE COMMENTS BASED ON |
| | THE PROPOSED ELECTRICAL RISER ARE MUTE |
| | AT THIS TIME AS SERVICE SHOWN IS NOT |
| | PERMITTED. PLEASE HOWEVER SEE SOME ITEMS |
| | BELOW AS ANY SERVICE UPGRADE WILL |
| | REQUIRE SOME OF THE SAME ITEMS. |
| | PLEASE SEE THE FOLLOWING. |
| | MISSING GAS BOND ON THE GROUNDING |
| | ELECTRODE SYSTEM, MISSING THE THE |
| | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN |
| | TO SUB PANELS. PLEASE SEE WHAT APPEARS |
| | TO BE A MISPRINT AS 1/4" FOR EQUIPMENT |
| | GROUND. |
| | PLEASE SEE MISSING AIC RATING FOR |
| | MAIN.(SHOWN FOR NEW SUB PANELS). |
| | |
| | |
| | 8) NOTE: OK, NO PANEL "E" SHOWN . |
| | |
| | 9) NOTE:OK. |
| | |
| | |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL DESIGN/PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |