Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop B
Sequence Number 2
Notes
Date Text
2006-11-14 13:15:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM THE PREVIOUS LIST, COMMENTS NOT ADDRESSED
  
 1.)DECLARE LEVEL OF ALTERATION FBC EB3
 AND INCLUDE FBC EB AS GOVERNING CODE.
 SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL
 OF ALTERATION.
  
 THE ARCHITECT DECLARED A LEVEL 3 AND FBC EB3.THE
 CORRECT CODE REFERENCE IS FBC 2004 EXISTING BUILDING.
 LEVEL 3 IS FOR OVER 50% IMPROVEMENT.THE PLAN SHOWS
 THAT LESS THAN 30% OF THE BUILDING IS BEING IMPROVED.
 IF THIS IS A LEVEL 3, PLEASE SHOW COMPLIANCE WITH ALL
 REQUIREMENTS.IF IT IS NOT,PLEASE REVISE THE NOTE.
 ALSO THIS IS A CHANGE OF OCCUPANCY; DESIGNER IS TO
 REVIEW REQUIREMENTS IN CHAPTER 8 FBC EB AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 2.)THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY BASED ON OCCUPATIONAL LICENSE
 ISSUED AND ON RECORD, SEE WWW.WPB.ORG
 (ONE STOP SHOP, OCCUPATIONAL LICENSES).
 THE PREVIOUS OCCUPANCY CLASSIFICATION
 APPEARS TO BE MERCANTILE.SEE FBC306.
  
 7.)PROVIDE A SURVEY FOR THIS PROPERTY
 TO DETERMINE COMPLIANCE WITH FBC TABLE
 602.
  
 8.)THE NORTH WALL APPEARS TO BE A
 TENANT SEPARATION WALL; WHAT OCCUPANCY CLASSIFICATION
 IS THAT SPACE?SHOW
 COMPLIANCE WITH FBC TABLE 302.3.2.
  
 THE PLAN WAS REVISED TO SHOW B OCCUPANCY.NO
 COMPLIANCE WITH FBC TABLE 302.3.2 SHOWN.
  
 10.)PROVIDE OVERALL DIMENSIONS OF THE
 SPACE ON THE LIFE SAFETY SHEET A120.1.
  
 11.)SEE FBC306.2.FOOD PROCESSING IS
 FACTORY OCCUPANCY CLASSIFICATION.
 CLARIFY WHY YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE FOOD PROCESSING AREA.
 SEE FBC302.1, PORTIONS OF STRUCTURES ARE
 TO BE CLASSIFIEDWITH RESPECT TO
 OCCUPANCY.
  
 16.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-103.1.
  
 17.)THE SQUARE FOOT AREA ON THE ENERGY
 CALC DOES NOT MATCH THE PLAN.NO
 UNCONDITIONED AREA SHOWN ON THE ENERGY
 CALC, UNCONDITIONED AREA SHOWN ON PLAN.
  
 NEW COMMENT:
  
 18.)INTERIOR FINISHES TO COMPLY WITH TABLE 803.5.
  
 19.)SEE ATTACHED FS 553.80(2)(B).
  
 18.)PROVIDE INFORMATION IN REGARDS TO ACCESSIBLE
 PARKING, ACCESSIBLE ROUTE.SEE FBC11-4.1.4.6(2).