| 2006-09-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | |
| | 1. PER TABLES 1004.1.2 AND 403.1 2-W/C'S |
| | AND SEPARATE FACILITIES ARE REQUIRED. - |
| | ALSO A DRINKING FOUNTATIN IS REQUIRED. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(2) A |
| | BUSINESS NUMBER IS |
| | REQUIRED. FS 481.219. |
| | |
| | 3. ALL ARCHITECTURAL SHEETS. ONE CAN NOT |
| | GLEAN THE REQUIRED INFORMATION FROM THE |
| | SEAL AS STATED IN 61G1-16.002(1). PLEASE |
| | RESEAL SO REQUIRED INFORMATION CAN BE |
| | READ. FS 481.2055. |
| | |
| | 4. THE GREASE INTERCEPTOR SHALL BE SIZED |
| | BY LYNN MASSON, ENVIRONMENTAL COMPLIANCE |
| | MANAGER. PLEASE CONTACT LYNN AT (561) |
| | 822-2271, OR (561) 822-2279 (FAX) OR |
| | E-MAIL AT [email protected]. |
| | |
| | 5. SHTS A125.1 AND A130.1. A125.1 SHOWS |
| | 1 TOILET ROOM WHEREAS SHT A130.1 SHOWS |
| | TWO TOILET ROOMS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 6. THE TWO PAGE "WORKSHEET" FROM DBPR |
| | PLAN REVIEW SHALL BE ATTACHED TO EACH |
| | SET OF PLANS. SECTION 106.1.3. |
| | |
| | 7. SHT P-1 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. TYPE OF GAS, (LP OR NATURAL) NOTE ON |
| | P-1 STATES LP OR NATURAL GAS. PLEASE |
| | CLARIFY. |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN |
| | ON THE GAS ISOMETRIC RISER DIAGRAM. |
| | |
| | 8. SHT P-3 GREASE INTERCEPTOR DETAIL. |
| | SEE ATTACHED SHEET FOR STANDARD GREAS |
| | INTERCEPTOR DETAIL. SEE MINIMUM |
| | REQUIREMENTS FOR SIDE WALLS, BOTTOM, |
| | ETC. NO FIBERGLASS INTERCEPTORS |
| | APPROVED. INTERCEPTOR SHALL BE MADE OF |
| | STEEL REINFORCED CONCRETE PER MUNICIPAL |
| | CODE SECTION 90-124(7)(F). PLEASE SUBMIT |
| | A MANUF. SPECIFICATION SHEET FOR GREASE INTERCEPTOR FOR |
| | APPROVAL. INDICATE MODEL |
| | NUMBER. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |