| Notes |
| Date |
Text |
| 2006-10-02 00:00:00 | PROVISO: | | | 1.DETAIL OF THE ROOF MOUNTED | | | CONDENSING UNIT SHOWN ON PLAN SHEET M-2 | | | DOES NOT INDICATE CLEARANCE BETWEEN THE | | | ROOF AND STAND AS REQUIRED PER 2004 FBC | | | TABLE 1509.7 | | | | | | 2.MAKEUP AIR FOR THE KITCHEN SHALL | | | COMPLY WITH 2004 FMC 508.1. | | | | | | 3.ADDITIONAL PERMITS REQUIRED FOR THE | | | HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURER'S SUBMITTAL DATA.PLEASE | | | INDICATE THE FOLLOWING INFORMATION WITH | | | REGARDS TO THE HOOD: | | | A) TERMINATION OF EXHAUST. PROVIDE | | | DISTANCE TO PROPERTY LINES, PARAPITS, | | | ADJOING BUILDINGS, INTAKE OPENINGS, | | | ETC. | | | B) PROVIDE EQUIPMENT SCHEDULE FOR THE | | | EXHAUST FAN. | | | C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL | | | D) VELOCITY THROUGH DUCT SHALL BE A | | | MINIMUM OF 1,500 FPM BUT NOT GREATER | | | THAN 2,500 FPM. | | | E) INDICATE CLEARANCES TO COMBUSTIBLES. | | | D) PROVIDE DETAIL FOR THE HANGING & | | | VIBRATION ISOLATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|