Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-02 00:00:00PROVISO:
 1.DETAIL OF THE ROOF MOUNTED
 CONDENSING UNIT SHOWN ON PLAN SHEET M-2
 DOES NOT INDICATE CLEARANCE BETWEEN THE
 ROOF AND STAND AS REQUIRED PER 2004 FBC
 TABLE 1509.7
  
 2.MAKEUP AIR FOR THE KITCHEN SHALL
 COMPLY WITH 2004 FMC 508.1.
  
 3.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER'S SUBMITTAL DATA.PLEASE
 INDICATE THE FOLLOWING INFORMATION WITH
 REGARDS TO THE HOOD:
 A) TERMINATION OF EXHAUST. PROVIDE
 DISTANCE TO PROPERTY LINES, PARAPITS,
 ADJOING BUILDINGS, INTAKE OPENINGS,
 ETC.
 B) PROVIDE EQUIPMENT SCHEDULE FOR THE
 EXHAUST FAN.
 C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL
 D) VELOCITY THROUGH DUCT SHALL BE A
 MINIMUM OF 1,500 FPM BUT NOT GREATER
 THAN 2,500 FPM.
 E) INDICATE CLEARANCES TO COMBUSTIBLES.
 D) PROVIDE DETAIL FOR THE HANGING &
 VIBRATION ISOLATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].