| Plan Review Notes For Permit 06081713 |
| Permit Number |
06081713 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-26 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE CLARIFY NOTE (5) ON LS PLAN | | | REF: DINING AND SEATING AREAS. IF NOT | | | APPLICABLE, PLEASE REMOVE FROM PLANS. | | | | | | 2) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR EXHAUST HOOD AND | | | SUPPRESSION SYSTEMS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|