Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-10 00:00:00*** UNSAT******
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION
 DOES NOT MATCH WITH THE LEGAL OWNER OF
 RECORD ON OUR SYSTEM, THE PALM BEACH
 COUNTY PROPERTY APPRAISER'S WEBSITE OR
 THE NOTICE OF COMMENCEMENT SUBMITTED.
 PLEASE CORRECT AND REVISE.
  
  
 2) NOTE: PLEASE SEE THE ADDRESS ON PLANS
 NEEDS TO CORRELATE WITH THE LEGAL
 ADDRESS OF PROPERTY. PLEASE KNOW THAT
 PERMIT APPLICATION WILL BE ROUTED TO THE ADDRESSING
 PERSON TO OBTAIN AN ADDRESS
 EXTENSION FOR THE TENANT SPACE.
 (UNIT/SUITER #).
 PLEASE BE SURE TO PLACE CORRECT ADDRESS
 ON PLANS ALONG WITH ANY REVISED/ NEW
 SUITE .
 FAC 61G1-16.004, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON ALL TITLE BLOCKS
 FOR ARCHITECTURAL FIRM. PLEASE SEE FAC
 61G1-16.004 AND FS 481.219.
 MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE THIS IS A TENANT
 SPACE PART OF A LARGER BUILDING AND THE
 NEW SERVICE AS SHOWN IS NOT GRANTED OR
 PERMITTED. 230.2
 ** PLEASE SEE AERIAL MAP PROVIDED.
 PLEASE SEE SERVICE LOCATION FOR THE
 EXISTING SERVICE IS TO BE SHOWN.
 PLEASE SEE SERVICE AS SHOWN IS BEING
 SHOWN AS AN OVERHEAD SERVICE LOCATED ON
 THE SOUTH SIDE OF BUILDING WHERE THE
 BUILDING FROM THE ADJOINING PROPERTY IS
 LOCATED. CLEARANCES AS REQUIRED UNDER
 THE FPL SERVICE GUIDELINES AND NEC ARE
 NOTMET IN EITHER CASE.
 PLEASE KNOW, THE EXISTING SERVICE FOR
 THE BUILDING MUST BE USED OR UPGRADED.
 PLEASE SEE THE 1HR SEPARATION DOES NOT
 MAKE THIS SPACE A SEPARATE BUILDING.
 PLEASE SEE FBC DEFINITIONS OF BUILDING,
 AND REQUIRED "FIRE WALL" IN ORDER TO
 BECOME A SEPARATE BUILDING. PLEASE SEE
 REQUIRED "FIRE WALL" WOULD BE A FOUR HR
 RATED WALL WHICH WOULD PERMIT THE
 COLLAPSE THE ADJOINING STRUCTURE WITHOUT
 AFFECT THE STRUCTURAL INTEGRITY OF THE
 ADJOINING REMAINING BUILDING.
  
 5) NOTE: PLEASE SEE THE SIGN CIRCUIT AS
 BEING SHOWN IS LOCATEDAT THE REAR DOOR
 WHICH BACKS UP TO THE FEC RAILROAD
 TRACKS. PLEASE SEE 600.5 WHICH REQUIRES
 THIS CIRCUIT TO BE LOCATED AT THE FRONT
 ENTRANCE SUBJECT TO PEDESTRIAN TRAFFIC.
  
 6) NOTE: IF TRYING TO OBTAIN COMPLIANCE
 WITH THE 2004 FBC CHAPTER 13,THE
 LIGHTING CONTROLS AS NOTED ARE NOT
 COMPLETE AT THIS TIME.PLEASE SHOW THE
 DETAIL FOR "SYSTEM" BEING PROPOSED.
 PLEASE ALSO INCLUDE EXISTING OFFICE
 AREAS ARE REQUIRED TO BE CONTROLLED BY
 THIS SYSTEM.
 PLEASE PROVIDE SCHEDULING, OVER RIDE
 DEVICES ALONG WITH MAX PERMITTED TIMES
 ON OVER RIDE DEVICES.
 (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON
 OCCUPANT SENSOR TYPES).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
  
 7) NOTE: PLEASE SEE COMMENTS BASED ON
 THE PROPOSED ELECTRICAL RISER ARE MUTE
 AT THIS TIME AS SERVICE SHOWN IS NOT
 PERMITTED. PLEASE HOWEVER SEE SOME ITEMS
 BELOW AS ANY SERVICE UPGRADE WILL
 REQUIRE SOME OF THE SAME ITEMS.
 PLEASE SEE THE FOLLOWING.
 MISSING GAS BOND ON THE GROUNDING
 ELECTRODE SYSTEM, MISSING THE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANELS. PLEASE SEE WHAT APPEARS
 TO BE A MISPRINT AS 1/4" FOR EQUIPMENT
 GROUND.
 PLEASE SEE MISSING AIC RATING FOR
 MAIN.(SHOWN FOR NEW SUB PANELS).
  
  
 8) NOTE: PLEASE SEE MISSING THE PANEL
 SCHEDULE FOR EXISTING PANEL "E" AND WHERE
 LOADS ARE DERIVED.
 408.4,310.16,240.4, 215.5 ETC
 FBC 106.1.2 ADMIN SECT.
  
 9) NOTE: PLEASE SEE PLANS SHALL STATE
 THE ADOPTED CODES RELEVANT TO PLANS AND
 DESIGN. PLEASE SEE 2002 NFPA-70, 2002
 NFPA-72, 2003 NFPA-101 (SHOWN ON "A"
 SHEETS) AND NFPA-96 2004 ARE ALL
 REQUIRED AT A MINIMUM.
 PLEASE SEE NOTES FROM OTHER TRADES FOR
 OTHER POSSIBLE RELEVANT CODES REQUIRED.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL DESIGN/PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved