Text |
| 2006-09-10 00:00:00 | *** UNSAT****** |
| | |
| | 1) NOTE: PLEASE SEE PERMIT APPLICATION |
| | DOES NOT MATCH WITH THE LEGAL OWNER OF |
| | RECORD ON OUR SYSTEM, THE PALM BEACH |
| | COUNTY PROPERTY APPRAISER'S WEBSITE OR |
| | THE NOTICE OF COMMENCEMENT SUBMITTED. |
| | PLEASE CORRECT AND REVISE. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE ADDRESS ON PLANS |
| | NEEDS TO CORRELATE WITH THE LEGAL |
| | ADDRESS OF PROPERTY. PLEASE KNOW THAT |
| | PERMIT APPLICATION WILL BE ROUTED TO THE ADDRESSING |
| | PERSON TO OBTAIN AN ADDRESS |
| | EXTENSION FOR THE TENANT SPACE. |
| | (UNIT/SUITER #). |
| | PLEASE BE SURE TO PLACE CORRECT ADDRESS |
| | ON PLANS ALONG WITH ANY REVISED/ NEW |
| | SUITE . |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE MISSING REQUIRED |
| | LICENSE INFORMATION ON ALL TITLE BLOCKS |
| | FOR ARCHITECTURAL FIRM. PLEASE SEE FAC |
| | 61G1-16.004 AND FS 481.219. |
| | MISSING THE REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE SEE THIS IS A TENANT |
| | SPACE PART OF A LARGER BUILDING AND THE |
| | NEW SERVICE AS SHOWN IS NOT GRANTED OR |
| | PERMITTED. 230.2 |
| | ** PLEASE SEE AERIAL MAP PROVIDED. |
| | PLEASE SEE SERVICE LOCATION FOR THE |
| | EXISTING SERVICE IS TO BE SHOWN. |
| | PLEASE SEE SERVICE AS SHOWN IS BEING |
| | SHOWN AS AN OVERHEAD SERVICE LOCATED ON |
| | THE SOUTH SIDE OF BUILDING WHERE THE |
| | BUILDING FROM THE ADJOINING PROPERTY IS |
| | LOCATED. CLEARANCES AS REQUIRED UNDER |
| | THE FPL SERVICE GUIDELINES AND NEC ARE |
| | NOTMET IN EITHER CASE. |
| | PLEASE KNOW, THE EXISTING SERVICE FOR |
| | THE BUILDING MUST BE USED OR UPGRADED. |
| | PLEASE SEE THE 1HR SEPARATION DOES NOT |
| | MAKE THIS SPACE A SEPARATE BUILDING. |
| | PLEASE SEE FBC DEFINITIONS OF BUILDING, |
| | AND REQUIRED "FIRE WALL" IN ORDER TO |
| | BECOME A SEPARATE BUILDING. PLEASE SEE |
| | REQUIRED "FIRE WALL" WOULD BE A FOUR HR |
| | RATED WALL WHICH WOULD PERMIT THE |
| | COLLAPSE THE ADJOINING STRUCTURE WITHOUT |
| | AFFECT THE STRUCTURAL INTEGRITY OF THE |
| | ADJOINING REMAINING BUILDING. |
| | |
| | 5) NOTE: PLEASE SEE THE SIGN CIRCUIT AS |
| | BEING SHOWN IS LOCATEDAT THE REAR DOOR |
| | WHICH BACKS UP TO THE FEC RAILROAD |
| | TRACKS. PLEASE SEE 600.5 WHICH REQUIRES |
| | THIS CIRCUIT TO BE LOCATED AT THE FRONT |
| | ENTRANCE SUBJECT TO PEDESTRIAN TRAFFIC. |
| | |
| | 6) NOTE: IF TRYING TO OBTAIN COMPLIANCE |
| | WITH THE 2004 FBC CHAPTER 13,THE |
| | LIGHTING CONTROLS AS NOTED ARE NOT |
| | COMPLETE AT THIS TIME.PLEASE SHOW THE |
| | DETAIL FOR "SYSTEM" BEING PROPOSED. |
| | PLEASE ALSO INCLUDE EXISTING OFFICE |
| | AREAS ARE REQUIRED TO BE CONTROLLED BY |
| | THIS SYSTEM. |
| | PLEASE PROVIDE SCHEDULING, OVER RIDE |
| | DEVICES ALONG WITH MAX PERMITTED TIMES |
| | ON OVER RIDE DEVICES. |
| | (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON |
| | OCCUPANT SENSOR TYPES). |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND |
| | .1.3. |
| | |
| | 7) NOTE: PLEASE SEE COMMENTS BASED ON |
| | THE PROPOSED ELECTRICAL RISER ARE MUTE |
| | AT THIS TIME AS SERVICE SHOWN IS NOT |
| | PERMITTED. PLEASE HOWEVER SEE SOME ITEMS |
| | BELOW AS ANY SERVICE UPGRADE WILL |
| | REQUIRE SOME OF THE SAME ITEMS. |
| | PLEASE SEE THE FOLLOWING. |
| | MISSING GAS BOND ON THE GROUNDING |
| | ELECTRODE SYSTEM, MISSING THE THE |
| | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN |
| | TO SUB PANELS. PLEASE SEE WHAT APPEARS |
| | TO BE A MISPRINT AS 1/4" FOR EQUIPMENT |
| | GROUND. |
| | PLEASE SEE MISSING AIC RATING FOR |
| | MAIN.(SHOWN FOR NEW SUB PANELS). |
| | |
| | |
| | 8) NOTE: PLEASE SEE MISSING THE PANEL |
| | SCHEDULE FOR EXISTING PANEL "E" AND WHERE |
| | LOADS ARE DERIVED. |
| | 408.4,310.16,240.4, 215.5 ETC |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 9) NOTE: PLEASE SEE PLANS SHALL STATE |
| | THE ADOPTED CODES RELEVANT TO PLANS AND |
| | DESIGN. PLEASE SEE 2002 NFPA-70, 2002 |
| | NFPA-72, 2003 NFPA-101 (SHOWN ON "A" |
| | SHEETS) AND NFPA-96 2004 ARE ALL |
| | REQUIRED AT A MINIMUM. |
| | PLEASE SEE NOTES FROM OTHER TRADES FOR |
| | OTHER POSSIBLE RELEVANT CODES REQUIRED. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL DESIGN/PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |