| 2006-09-18 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)DECLARE LEVEL OF ALTERATION FBC EB3 |
| | AND INCLUDE FBC EB AS GOVERNING CODE. |
| | SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL |
| | OF ALTERATION. |
| | |
| | 2.)THIS APPEARS TO BE A CHANGE OF |
| | OCCUPANCY BASED ON OCCUPATIONAL LICENSE |
| | ISSUED AND ON RECORD, SEE WWW.WPB.ORG |
| | (ONE STOP SHOP, OCCUPATIONAL LICENSES). |
| | THE PREVIOUS OCCUPANCY CLASSIFICATION |
| | APPEARS TO BE MERCANTILE.SEE FBC306. |
| | |
| | 3.)THE COMPANY RJS ARCHITECTS, INC. IS |
| | REQUIRED TO HAVE AN ARCHITECT BUSINESS |
| | LICENSE.I WAS UNABLE TO LOCATE THIS ON |
| | WWW.MYFLORIDALICENSE.COM.PLEASE |
| | PROVIDE THE LICENSE NUMBER ON THE PLAN |
| | FAC61G1-16.003,004. |
| | |
| | 4.)SEE COMMENTS FROM ADDRESSING AND |
| | ELECTRIC REGARDING THE BUILDING ADDRESS |
| | ON THE PLAN.PLEASE RESOLVE AND REVISE |
| | PLAN IF NECESSARY. |
| | |
| | 5.)A120.1 IS USED TWICE, BOTH MARKED |
| | LIFE SAFETY PLAN, BUT ONE IS A DEMO |
| | PLAN. |
| | |
| | 6.)BUILDING CODE CHECKLIST, PROVIDE |
| | THE TOTAL BUILDING AREA, BUILDING |
| | HEIGHT, OTHER TENANT SPACES AND |
| | OCCUPANCY TO DETERMINE COMPLIANCE WITH |
| | FBC TABLE 503. |
| | |
| | 7.)PROVIDE A SURVEY FOR THIS PROPERTY |
| | TO DETERMINE COMPLIANCE WITH FBC TABLE |
| | 602. |
| | |
| | 8.)THE NORTH WALL APPEARS TO BE A |
| | TENANT SEPARATION WALL; WHAT OCCUPANCY |
| | CLASSIFICATION IS THAT SPACE?SHOW |
| | COMPLIANCE WITH FBC TABLE 302.3.2. |
| | |
| | 9.)A120.1 SHOWS 1 AND 2 HOUR |
| | PENETRATION DETAILS; WHERE WILL THIS BE |
| | INSTALLED?NO FIRE RATED WALLS ARE |
| | SHOWN ON THE PLAN.SHOW ALL REQUIRED |
| | FIRE SEPARATIONS REQUIRED ON THE PLAN. |
| | |
| | 10.)PROVIDE OVERALL DIMENSIONS OF THE |
| | SPACE ON THE LIFE SAFETY SHEET A120.1. |
| | |
| | 11.)SEE FBC306.2.FOOD PROCESSING IS |
| | FACTORY OCCUPANCY CLASSIFICATION. |
| | CLARIFY WHY YOU HAVE DECLARED BUSINESS |
| | OCCUPANCY FOR THE FOOD PROCESSING AREA. |
| | SEE FBC302.1, PORTIONS OF STRUCTURES ARE |
| | TO BE CLASSIFIEDWITH RESPECT TO |
| | OCCUPANCY. |
| | |
| | 12.)SEE FBC302.1, FBC302.2.ADDRESS |
| | THE MIXED USE OF THE OFFICE AREAS |
| | (BUSINESS) AND THE PROCESSING AREA |
| | (FACTORY).SHOW COMPLIANCE WITH |
| | FBC302.2 OR SHOW REQUIRED FIRE |
| | SEPARATION. |
| | |
| | 13.)LIFE SAFETY NOTE #5 REFERS TO |
| | DINING AND SEATING AREAS.NONE SHOWN ON |
| | THE PLAN AND THIS CONFLICTS WITH THE |
| | NOTE ON THE COVER SHEET WHICH STATES |
| | THAT ALL FOOD WILL BE CONSUMED OFF |
| | PREMISES.PLEASE CLARIFY. |
| | |
| | 14.)NOTE 1 HAS REFERENCES TO A, E, I, |
| | R OCCUPANCIES.PLEASE REMOVE AS THEY |
| | ARE NOT PERTINENT TO THIS JOB AND DO NOT |
| | APPEAR TO BE FBC2004 NOTES. |
| | |
| | 15.)RESTROOM DOOR 3 BLOCKS OVER HALF |
| | THE REQUIRED EGRESS WIDTH, SEE |
| | FBC1005.2. |
| | |
| | 16.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC FBC13-103.1. |
| | |
| | 17.)THE SQUARE FOOT AREA ON THE ENERGY |
| | CALC DOES NOT MATCH THE PLAN.NO |
| | UNCONDITIONED AREA SHOWN ON THE ENERGY |
| | CALC, UNCONDITIONED AREA SHOWN ON PLAN. |