Plan Review Notes
Plan Review Notes For Permit 06081713
Permit Number 06081713
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DECLARE LEVEL OF ALTERATION FBC EB3
 AND INCLUDE FBC EB AS GOVERNING CODE.
 SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL
 OF ALTERATION.
  
 2.)THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY BASED ON OCCUPATIONAL LICENSE
 ISSUED AND ON RECORD, SEE WWW.WPB.ORG
 (ONE STOP SHOP, OCCUPATIONAL LICENSES).
 THE PREVIOUS OCCUPANCY CLASSIFICATION
 APPEARS TO BE MERCANTILE.SEE FBC306.
  
 3.)THE COMPANY RJS ARCHITECTS, INC. IS
 REQUIRED TO HAVE AN ARCHITECT BUSINESS
 LICENSE.I WAS UNABLE TO LOCATE THIS ON
 WWW.MYFLORIDALICENSE.COM.PLEASE
 PROVIDE THE LICENSE NUMBER ON THE PLAN
 FAC61G1-16.003,004.
  
 4.)SEE COMMENTS FROM ADDRESSING AND
 ELECTRIC REGARDING THE BUILDING ADDRESS
 ON THE PLAN.PLEASE RESOLVE AND REVISE
 PLAN IF NECESSARY.
  
 5.)A120.1 IS USED TWICE, BOTH MARKED
 LIFE SAFETY PLAN, BUT ONE IS A DEMO
 PLAN.
  
 6.)BUILDING CODE CHECKLIST, PROVIDE
 THE TOTAL BUILDING AREA, BUILDING
 HEIGHT, OTHER TENANT SPACES AND
 OCCUPANCY TO DETERMINE COMPLIANCE WITH
 FBC TABLE 503.
  
 7.)PROVIDE A SURVEY FOR THIS PROPERTY
 TO DETERMINE COMPLIANCE WITH FBC TABLE
 602.
  
 8.)THE NORTH WALL APPEARS TO BE A
 TENANT SEPARATION WALL; WHAT OCCUPANCY
 CLASSIFICATION IS THAT SPACE?SHOW
 COMPLIANCE WITH FBC TABLE 302.3.2.
  
 9.)A120.1 SHOWS 1 AND 2 HOUR
 PENETRATION DETAILS; WHERE WILL THIS BE
 INSTALLED?NO FIRE RATED WALLS ARE
 SHOWN ON THE PLAN.SHOW ALL REQUIRED
 FIRE SEPARATIONS REQUIRED ON THE PLAN.
  
 10.)PROVIDE OVERALL DIMENSIONS OF THE
 SPACE ON THE LIFE SAFETY SHEET A120.1.
  
 11.)SEE FBC306.2.FOOD PROCESSING IS
 FACTORY OCCUPANCY CLASSIFICATION.
 CLARIFY WHY YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE FOOD PROCESSING AREA.
 SEE FBC302.1, PORTIONS OF STRUCTURES ARE
 TO BE CLASSIFIEDWITH RESPECT TO
 OCCUPANCY.
  
 12.)SEE FBC302.1, FBC302.2.ADDRESS
 THE MIXED USE OF THE OFFICE AREAS
 (BUSINESS) AND THE PROCESSING AREA
 (FACTORY).SHOW COMPLIANCE WITH
 FBC302.2 OR SHOW REQUIRED FIRE
 SEPARATION.
  
 13.)LIFE SAFETY NOTE #5 REFERS TO
 DINING AND SEATING AREAS.NONE SHOWN ON
 THE PLAN AND THIS CONFLICTS WITH THE
 NOTE ON THE COVER SHEET WHICH STATES
 THAT ALL FOOD WILL BE CONSUMED OFF
 PREMISES.PLEASE CLARIFY.
  
 14.)NOTE 1 HAS REFERENCES TO A, E, I,
 R OCCUPANCIES.PLEASE REMOVE AS THEY
 ARE NOT PERTINENT TO THIS JOB AND DO NOT
 APPEAR TO BE FBC2004 NOTES.
  
 15.)RESTROOM DOOR 3 BLOCKS OVER HALF
 THE REQUIRED EGRESS WIDTH, SEE
 FBC1005.2.
  
 16.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-103.1.
  
 17.)THE SQUARE FOOT AREA ON THE ENERGY
 CALC DOES NOT MATCH THE PLAN.NO
 UNCONDITIONED AREA SHOWN ON THE ENERGY
 CALC, UNCONDITIONED AREA SHOWN ON PLAN.