| Plan Review Notes For Permit 06081709 |
| Permit Number |
06081709 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-08 00:00:00 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. NEED TO SHOW SILT FENCE AROUND SITE | | | FOR POLLUTION PREVENTION PLANS, ETC., | | | 2. PERVIOUS, IMPERVIOUS AREA, STORM | | | WATER CAL.,CRITERIA FOR RUNOFF CAL., | | | 3. PL. SHOW CONTROL STRUCTURES IF ANY, & | | | DETAILS,EXFILTRATION TRENCHES, IF | | | ANY.WET OR DRY RETENTION AREAS, WE LIKE | | | TO KNOW HOW YOU ARE GOING TO TAKE CARE | | | OF STORM WATER. PLEASE PROVIDE SFWMD | | | PERMIT, GEOTECH REPORT ETC.,TO US. | | | 4. CITY OF WPB DETAILS STANDARDS,MUST BE | | | INCLUDED IN THE DRAWINGS, FOR SIDE | | | WALK,PARKINGS, PER ADA STANDARDS, | | | 5. FIRST FLOOR ELEVATION MUST MEET FL | | | BUILDING CODES. | | | 6. DUMPSTER ENCLOSURE DETAILS PER CITY | | | OF WPB DETAILS IN THE DRAWINGS. | | | | | | PLEASE RESPOND EACH ABOVE ITEM | | | SEPARATELY IN YOUR REPLY FOR | | | ENGINEERING. THANKS, RASIK CHOKSHI | | | 805-6723 |
|