| 2006-09-28 00:00:00 | ******DENIED 3RD TIME****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR GAS PLAN REVIEW FROM THE |
| | PRIVIOUS COMMENTS: |
| | |
| | 1. (OK) |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED DRAWING IS STILL |
| | NOT AN ISOMETRIC AND DOES NOT CLEARLY |
| | SHOW ALL CUT SECTIONS OF PIPE AND |
| | CORRESPONDING LENGTHS. PLEASE REFERENCE |
| | THE ATTACHED ISOMETIC EXAMPLE FOR |
| | RESUBMITTAL AND PLEASE INDICATE THE |
| | ABOVE GROUND PIPE LENGTHS. |
| | |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: THE RESUBMITTED DRAWING DOES NOT |
| | INDICATE ALL THE PIPE MATERIALS AND |
| | SIZES PLEASE INDICATE THE ABOVE GROUND |
| | PIPE MATERIALS AND SIZES FOR THE |
| | RESUBMITTAL. |
| | |
| | 4. (OK) |
| | |
| | 5. (OK) |
| | |
| | 6. (OK) |
| | |
| | 7. (OK) |
| | |
| | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: STILL NEED MANUFAFTURER CUT SHEETS |
| | OF 1ST AND 2ND STAGE REGULATORS. |
| | |
| | 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | NOTE: DRAWINGS STILL DON'T HAVE THE |
| | PRINTED AND SIGNED NAME OF THE PERSON |
| | TAKING RESPONSIBILITY OF DRAWINGS AND |
| | THE DATE. |
| | |
| | END OF COMMENTS: |
| | |