| Plan Review Notes For Permit 06081660 |
| Permit Number |
06081660 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-06 00:00:00 | *** DENIED *** | | | 1) SITE PLAN SHOWS A FORM BOARD | | | LOCATION, PLEASE SHOW WHAT IS TO BE | | | BUILT ON THET SITE. | | | | | | 2) GENERATOR LOCATION NEEDS TO BE | | | LABELED. | | | | | | 3) PLEASE SHOW BUILDING OPENINGS ON SITE | | | PLAN. GENERATOR EXHUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS). PER | | | 2004 FBC/M 401.5.1 . | | | | | | 4) GENERATOR MAY BE TO CLOSE TO | | | STRUCTURE THAT WILL BE BUILT ON FORM | | | BOARD LOCATION. | | | | | | 5)NEED TO SUBMIT TWO COPIES OF ALL | | | DOCUMENTS. ALL INFORMATION, | | | DRAWINGS,SPECIFICATIONS AND ACCOMPANYING | | | DATA SHELL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. PER 2004 WPB(A) FBC 106.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | | | | |
|